144 H9 ASD Installation and Operation Manual

Creeping Time

Program Torq ue Torque Control
Once the Creep function of F346 is activated, this paramet e r de te rm i ne s the
duration of activation of the Creep function.
Direct Access Number — F347
Parameter Type — Numeri cal
Factory Default — 0.10
Changeable During Run — Yes
Minimum — 0.0
Maximum — 2.50
Units — Seconds

Braking Time Learning Function

Program Torq ue Torque Control
This parameter is use d to establish approxima te settings for paramet ers F343,
F345, F346, and F347.
Note: Setting this parameter should be done using a l ight load only.
Set this parameter to Brake Signal Learning. Provide a Run command. The
aforementioned param eters will receive ap proximate values. App lication-
specific adjustments may be required when done.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F348
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes

Accel/Decel Suspend

Program Fundamental Accel/Decel #1 Settings
To maintain a constant spee d setting while runnin g, this parameter may b e used
to suspend speed changes for a user-set length of time.
The Accel/Decel Suspend function is enabled by setting this parameter to
either Terminal Board Input or to F350F353.
Selecting Terminal Board Input at this parameter req u ires that a discrete input
terminal be set to Dwell Signal (see Table 5 on pg. 236 for a listing of available
settings). Upon activatio n of the Dwell Signal terminal the output frequency
remains at the at-activation speed for the duration of the activation. When
deactivated the programmed accel or decel ramp resumes.
Selecting F350F353 at this parameter requires that the acceleration and/or
the deceleration Suspend Frequency and Suspend Time settings be completed
at F350, F351, F352, and F353. Upon reaching the fr equency setting of F350
(Accel) or F352 (Decel), the Accel/Decel ra mp will cease and th e output
frequency will hold at the threshold frequency setting for the time setting of
F351 for Acceleration or F353 for dec el eration.
Settings:
0 — Off
1 — F350F353 Settings
2 — Terminal Board Input
Direct Access Number — F349
Parameter Type — Selection List
Factory Default — Off
Changeable During Run — Yes
F347 F349