F005

F006

MFM Output Terminal Function

Program Terminal Analog Output Terminals

This parameter is used to set the output function of the FM analog output terminal. The FM output terminal produces an output current or voltage that is proportional to the magnitude of the function assigned to this terminal (select current or voltage at F681). The available assignments for this output terminal are listed in Table 6 on pg. 239.

Note: To read voltage at this terminal connect a 100 – 500Ω resistor from

the FM (+) terminal to the CC (-) terminal. Using a voltmeter read the voltage across the 100 – 500Ω resistor.

To read current at this terminal connect a 100 – 500Ω resistor from the FM (+) terminal through a series Ammeter to the CC (-) terminal.

The FM analog output has a maximum resolution of 1/1024 and a maximum load rating of 500 ohms.

Direct Access Number — F005 Parameter Type — Selection List Factory Default — DC (Bus) Voltage Changeable During Run — Yes

FM Terminal Setup Parameters

F005

— Set FM Function

F006

— Calibrate FM Terminal

F681

— Voltage/Current Output Switching Selection

F682

— Output Response Polarity Selection

F683

— Set Zero Level

FM Output Terminal Adjustment

Direct Access Number — F006

Program Terminal Analog Output Terminals

Parameter Type — Numerical

This parameter is used to calibrate the FM analog output.

Factory Default — 493

Changeable During Run — Yes

To calibrate the FM analog output, connect a meter (current or voltage) as

Minimum — 1

described at F005.

 

With the drive running at a known value (e.g., output frequency), adjust this

Maximum — 1280

 

parameter until the assigned function produces the desired DC level output at

 

the FM output terminal.

 

See F005 for more information on this setting.

 