Power Connection Requirements
Connect the
If multiple conductors are used in parallel for the input or output power and it is necessary to use separate conduits, each parallel set shall have its own conduit and not share its conduit with other parallel sets — i.e., place U1, V1, and W1 in one conduit and U2, V2, and W2 in another (refer to NEC Article 300.20 and Article 310.4). National and local electrical codes should be referenced if three or more power conductors are run in the same conduit (refer to 2005 NEC Article 310 adjustment factors).
Note: National and local codes should be referenced when running more than three conductors in the same conduit.
Install a molded case circuit breaker (MCCB) or fuse between the
The H9 ASD is designed and tested to comply with UL Standard 508C. Modifications to the ASD system or failure to comply with the short circuit protection requirements outlined in this manual may disqualify the UL rating. See Table 22 on pg. 267 for
As a minimum, the installation of the H9 ASD shall conform to 2005 NEC Article 110, the Occupational Safety and Health Administration requirements, and to any other local and regional industry codes and standards.
Note: In the event that the motor rotates in the wrong direction when powered up, reverse any two of the three H9 ASD output power leads (U, V, or W) connected to the motor.
Figure 3. H9 ASD/Motor typical connection scheme.