Selection of OUT Terminal

Program Terminal Analog Output Terminals

This parameter is used to enable the OUT1 and OUT2 output terminals, or the FP output terminal by selecting Logic Output or Pulse Train Output, respectively.

Note: The Logic output and the Pulse Train output may not be used simultaneously.

Direct Access Number — F669

Parameter Type — Selection List

Factory Default — Pulse Train Output

Changeable During Run — No

If Logic Output is selected the OUT1 and OUT2 (O1A/O1B and O2A/O2B) output contacts of the Terminal Board are enabled to function as described in parameter F130.

The OUT1 and OUT2 terminals may be used simultaneously and they may be assigned different functions.

If Pulse Train Output is selected the FP output terminal of the Terminal Board is enabled to function as configured in F676 and F677.

 

Settings:

 

 

 

0 — Logic Output

 

 

 

1 — Pulse Train Output

 

 

M

 

 

 

AM Output Terminal Function

Direct Access Number —

F670

 

Program Terminal Analog Output Terminals

Parameter Type — Selection List

 

This parameter is used to set the output function of the AM analog output

Factory Default — Output Current

 

Changeable During Run — Yes

 

terminal. The AM analog output terminal produces an output current that is

 

 

 

 

proportional to the magnitude of the function assigned to this terminal. The

 

 

 

available assignments for this output terminal are listed in Table 6 on pg. 239.

 

 

 

Note: To read current at this terminal connect a 100 – 500Ω resistor from

 

 

 

the AM (+) terminal through the series Ammeter to the CC (-)

 

 

 

terminal.

 

 

 

The FM analog output has a maximum resolution of 1/1024 and a

 

 

 

maximum load rating of 500 ohms.

 

 

 

AM Terminal Setup Parameters

 

 

 

F670 — Set AM Function

 

 

 

F671 — Calibrate AM Terminal

 

 

 

F685 — Output Response Polarity Selection

 

 

 

F686 — Set Zero Level

 

 

 

 

 

 

 

AM Output Terminal Adjustment

Direct Access Number —

F671

 

Program Terminal Analog Output Terminals

Parameter Type — Numerical

 

 

Factory Default — 512

 

This parameter is used to calibrate the AM analog output.

Changeable During Run — Yes

To calibrate the AM analog output, connect an ammeter as described at

parameter F670.

Minimum — 1

With the drive running at a known value (e.g., output frequency), adjust this parameter until the assigned function (parameter F670) produces the desired DC level output at the AM output terminal.

See F670 for more information on this setting.

Maximum — 1280