194 H9 ASD Installation and Operation Manual

Selection of OUT Terminal

Program Terminal Analog Output Terminals
This parameter is use d to enable the OUT1 and OUT2 output terminals, or the
FP output terminal by selecting Logic Output or Pulse Train Output,
respectively.
Note: The Logic output and the Pulse Train output may not be used
simultaneously.
If Logic Output is selected the OUT1 and OUT2 (O1A/O1B and O2A/O2B)
output contacts of the Terminal Board are enabled to function as described in
parameter F130.
The OUT1 and OUT2 terminals may be used simultaneo us ly an d th e y may be
assigned different func tions.
If Pulse Train Output is selected the FP output terminal of the Terminal Board
is enabled to function as configured in F676 and F677.
Settings:
0 — Logic Output
1 — Pulse Train Output
Direct Access Number — F669
Parameter Type — Selection List
Factory Default — Pulse Train Output
Changeable During Run — No

AM Output Terminal Function

Program Terminal Analog Output Terminals
This parameter is used to set the output function of the AM analog output
terminal. The AM analog output terminal produces an output current that is
proportional to the magnitude of the function assigned to this terminal. The
available assignments for this output terminal are listed in T able 6 on pg. 239.
Note: To read current at this terminal connect a 100 – 500
Ω
resistor from
the AM (+) terminal through the series Ammeter to the CC (-)
terminal.
The FM analog output has a maximum resolution of 1/1 024 and a
maximum load rating of 500 ohms.
AM Terminal Setup Parameters
F670 — Set AM Function
F671 — Calibrate AM Terminal
F685 — Output Response Polarity Selection
F686 — Set Zero Level
Direct Access Number — F670
Parameter Type — Selection List
Factory Default — Output Current
Changeable During Run — Yes

AM Output Terminal Adjustment

Program Terminal Analog Output Terminals
This parameter is use d to calibrate the AM analog output.
To calibrate the AM analog output, connect an ammeter as described at
parameter F670.
With the drive running at a known value (e.g., output frequency), adjust this
parameter until the assigne d fun c tion (parameter F670) produces the desired
DC level output at the AM output terminal.
See F670 for more information on this setting.
Direct Access Number — F671
Parameter Type — Numeri cal
Factory Default — 512
Changeable During Run — Yes
Minimum — 1
Maximum — 1280

AM

F669 F671