F178

 

F181

 

 

 

Base Frequency 4

Direct Access Number —

F178

Program Motor Motor Set #4

Parameter Type — Numerical

The Base Frequency 4 setting is the frequency at which the output voltage of

Factory Default — 60.0

 

Changeable During Run — Yes

the ASD reaches its maximum setting. The Base Frequency Voltage 4

 

 

parameter is set at F179.

Minimum — 25.00

 

This parameter is used only when the parameters for motor set #4 are

Maximum — 299.0

 

configured and selected. Motor set #4 may be selected by a properly configured

Units — Hz

 

input terminal (see Table 5 on pg. 236).

 

 

 

For proper motor operation, the Base Frequency should be set for the name-

 

 

plated frequency of the motor.

 

 

 

 

 

Base Frequency Voltage 4

Direct Access Number —

F179

Program Motor Motor Set #4

Parameter Type — Numerical

The Base Frequency Voltage 4 is the Motor #4 output voltage at the Base

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Frequency (F178). Regardless of the programmed value, the output voltage

 

 

cannot be higher than the input voltage.

Minimum — 50.0

 

The actual output voltage will be influenced by the input voltage of the ASD

Maximum — 660.0

 

and the Supply Voltage Compensation setting (F307).

Units — Volts

 

 

 

This parameter is used only when the parameters for motor set #4 are configured and selected. Motor set #4 may be selected by a properly configured input terminal (see Table 5 on pg. 236).

Manual Torque Boost 4

Program Motor Motor Set #4

The Manual Torque Boost 4 function is used to increase the low frequency torque for high inertia loads by increasing the output voltage at frequencies below ½ of the #4 Base Frequency setting (F178).

See parameter F016 (Manual Torque Boost 1) for an explanation of torque boost.

This parameter is used only when the parameters for motor set #4 are configured and selected. Motor set #4 may be selected by a properly configured input terminal (see Table 5 on pg. 236).

Direct Access Number — F180

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.0

Maximum — 30.0

Units — %

Motor Overload Protection Level 4

Program Motor Motor Set #4

The Motor 4 Overload Protection Level parameter specifies the motor overload current level for motor set #4. This value is entered as either a percentage of the full load rating of the ASD or as the FLA of the motor.

The unit of measurement for this parameter may be set to Amps (A/V) or it may be set as a percentage of the ASD rating. The name-plated FLA of the motor may be entered directly when Amps is selected as the unit of measurement (see F701 to change the display unit).

The Motor 4 Overload Protection Level setting will be displayed in Amps if the EOI display units are set to A/V rather than %.

Direct Access Number — F181

Parameter Type — Numerical

Factory Default — 100.0

Changeable During Run — Yes

Minimum — 10

Maximum — 100

Units — %

100

H9 ASD Installation and Operation Manual

Page 108
Image 108
Toshiba H9 operation manual F178 F181, Direct Access Number F178, Program ⇒ Motor ⇒ Motor Set #4, Direct Access Number F179