F100

F105

ow Speed

Low-Speed Signal Output Frequency

Program Terminal Reach Settings

The Low Speed Signal Output Frequency parameter sets a frequency threshold that activates the assigned output terminal for the duration that the ASD output is at or above this setting (see Table 8 on pg. 241 for the available output assignments).

Direct Access Number — F100

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (F011)

Units — Hz

each requency

Speed Reach Frequency

Program Terminal Reach Settings

The Speed Reach Frequency sets a frequency threshold that, when reached or is within the bandwidth specified by parameter F102, activates the assigned output terminal for the duration that the ASD output is within the bandwidth specified (see Table 8 on pg. 241 for the available output assignments).

Direct Access Number — F101

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (F011)

Units — Hz

Speed Reach Detection Band

Program Terminal Reach Settings

This parameter sets the bandwidth of the Speed Reach Frequency (F101) setting.

Direct Access Number — F102

Parameter Type — Numerical

Factory Default — 2.50

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (F011)

Units — Hz

Forward/Reverse Run Priority Selection

Program Terminal Input Special Functions

The Forward/Reverse Priority Selection determines the operation of the ASD if the F and R control terminals are activated simultaneously.

Settings:

0 — Reverse

1 — Suspend

The waveforms shown depict the motor response for all combinations of the F and R terminal settings if the Reverse option is chosen.

The Suspend setting will decelerate the motor to a stop regardless of the rotation direction when both the F and R control terminals are activated.

Direct Access Number — F105

Parameter Type — Selection List

Factory Default — Suspend

Changeable During Run — No

Simultaneous F and R activation.

86

H9 ASD Installation and Operation Manual

Page 94
Image 94
Toshiba H9 operation manual F100 F105, Low-Speed Signal Output Frequency, Speed Reach Frequency, Speed Reach Detection Band