86 H9 ASD Installation and Operation Manual

Low-Speed Signal Output Frequency

Program Terminal Reach Settings
The Low Speed Signal Output Frequency parameter sets a frequency
threshold that activates the assigned output terminal for the duration that the
ASD output is at or a bove this setting (see Table 8 on pg. 241 for the available
output assignments).
Direct Access Number — F100
Parameter Type — Numeri cal
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz

Speed Reach Frequency

Program Terminal Reach Settings
The Speed Reach Frequency sets a frequency threshold that, when reached or
is within the bandwid th specified by paramete r F102, activates the assigned
output terminal for the duration that the ASD output is within the bandwidth
specified (see Table 8 on pg. 24 1 for the available output assignments).
Direct Access Number — F101
Parameter Type — Numeri cal
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz

Speed Reach Detection Band

Program Terminal Reach Settings

This parameter sets th e bandwidth of the Speed Reach Frequency (F101)
setting.
Direct Access Number — F102
Parameter Type — Numeri cal
Factory Default — 2.50
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz

Forward/Reverse Run Priority Selection

Program Terminal Input Special Functions
The Forward/Reverse Priority Selection determines the operation of the ASD
if the F and R control terminal s are activated simultaneously.
Settings:
0 — Reverse
1 — Suspend
The waveforms shown depict the motor response for all combinations of the F
and R terminal settings if the R everse option is chosen.
The Suspend setting will decelerate the motor to a sto p reg ar d le ss of th e
rotation direction when both the F and R control terminals are activated.
Direct Access Number — F105
Parameter Type — Selection List
Factory Default — Suspend
Changeable During Run — No
Simultaneous F and R activation.

Low Speed

Reach

Fr

equen

cy

F100 F105