F303 | F303 |
Retry Selection
Program ⇒ Protection ⇒ Retry/Restart
After a trip has occurred, this parameter sets the number of times that an automatic system restart is attempted for a qualified trip.
The trip conditions listed below will not initiate the automatic Retry/Restart function:
•Input Phase Loss (Input Phase Failure)
•Output Phase Loss (Output Phase Failure)
•Output Current Protection Fault
•Output Current Detector error
•Load side overcurrent at start
•Earth Fault (Ground Fault)
•Overcurrent During Acceleration
•Arm Overcurrent at
•DBR Resistor Overcurrent
•Low Current
•Voltage Drop In Main Circuit
•EEPROM Data Fault (EEPROM Fault)
•Flash Memory/Gate
•CPU Fault
•Emergency Off (EMG)
•Communication Error
•Option Fault
•Sink/Source Setting Error
•Overspeed Error
•Overtorque
•Key Error
•External Thermal Error
•
See the section titled System Setup Requirements on pg. 8 for more information on this setting.
Direct Access Number — F303
Parameter Type — Numerical
Factory Default — 00
Changeable During Run — Yes
Minimum — 00
Maximum — 10
H9 ASD Installation and Operation Manual | 135 |