Forward Run/Reverse Run Disable

Program Frequency Forward/Reverse Disable

This parameter Enables/Disables the Forward Run or Reverse Run mode.

If either direction is disabled, commands received for the disabled direction will not be recognized.

If both directions are disabled, the received direction command will determine the direction of the motor rotation.

Settings:

0 — Off

1 — Disable Reverse Run

2 — Disable Forward Run

Direct Access Number — F311

Parameter Type — Selection List

Factory Default — Off

Changeable During Run — No

Random Mode

Program Protection Retry/Restart

This parameter adjusts the carrier frequency randomly. This feature is effective in minimizing the negative effects of mechanical resonance.

Settings:

0 — Disabled

1 — Enabled

Direct Access Number — F312

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No

Carrier Frequency Control Mode

Direct Access Number —

F316

Program Special Carrier Frequency

Parameter Type — Selection List

This parameter provides for the automatic decrease of the carrier frequency.

Factory Default — Valid Decrease and

No Limit

 

Select 1 to decrease the Carrier Frequency setting as a function of an

Changeable During Run — Yes

increased current requirement.

 

 

Selection 2 or 3 may also include an output voltage drop as a function of an

 

 

increased current requirement. The Carrier Frequency should be set below

 

 

4 kHz.

 

 

Settings:

 

 

0 — No Decrease and No Limit

 

 

1 — Valid Decrease and No Limit

 

 

2 — No Decrease and Limit Small Pulse

 

 

4 — Valid Decrease and Limit Small Pulse

 

 

 

 

 

Synchronized Deceleration Time

Direct Access Number —

F317

Program Protection Undervoltage/Ridethrough

Parameter Type — Numerical

In the event that the Ridethrough function activates in a multiple-motor

Factory Default — 2.0

 

Changeable During Run — Yes

application it will be necessary to manage the stopping motors synchronously

 

 

as not to damage the product being processed (e.g., wire spools, bobbin winder

Minimum — 0.1

 

for textile machines, etc.).

Maximum — 6000.0

 

 

 

This parameter is used to minimize the product breakage during a momentary

Units — Seconds

power outage. This function stops multiple machines simultaneously or makes

 

them reach their respective command frequencies simultaneously by regulating

 

their deceleration times.

 

See parameter F302 for more information on this setting.

 