Toshiba H9 operation manual F402 F409, Motor Rated Capacity, Motor Rated Current, Motor Rated RPM

Models: H9

1 289
Download 289 pages 12.38 Kb
Page 160
Image 160

F402

F409

 

 

 

Autotuning 2

Direct Access Number — F402

Program Motor Vector Motor Model

Parameter Type — Selection List

This parameter introduces a thermal element into the autotuning equation and is

Factory Default — Off

Changeable During Run — No

used to automatically adjust the Autotune parameter values as a function of

 

 

increases in the temperature of the motor.

 

 

Settings:

0 — Off

1 — Self-Cooled Motor Tuning

2 — Forced Air Cooled Motor Tuning

Motor Rated Capacity

Direct Access Number — F405

Program Motor Vector Motor Model

Parameter Type — Numerical

This parameter is used to set the (nameplated) rated capacity of the motor being

Factory Default — 11.0

Changeable During Run — Yes

used.

 

 

Minimum — 0.1

 

Maximum — 500.00

 

Units — kW

Motor Rated Current

Program Motor Vector Motor Model

This parameter is used to set the (nameplated) current rating of the motor being used.

Direct Access Number — F406

Parameter Type — Numerical

Factory Default — 20.3

Changeable During Run — Yes

Minimum — 0.1

Maximum — 2000.0

Units — Amps

Motor Rated RPM

Direct Access Number — F407

Program Motor Vector Motor Model

Parameter Type — Numerical

This parameter is used input the (nameplated) rated speed of the motor.

Factory Default — 1730

Changeable During Run — Yes

 

 

Minimum — 100

 

Maximum — 60000

 

Units — RPM

Base Frequency Voltage 1

Program Vector Vector Motor Model

The Motor #1 Base Frequency Voltage 1 is the Motor #1 output voltage at the Base Frequency (F014). Regardless of the programmed value, the output voltage cannot be higher than the input voltage.

The actual output voltage will be influenced by the input voltage of the ASD and the Supply Voltage Correction setting (F307).

Direct Access Number — F409

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 50.0

Maximum — 660.0

Units — Volts

152

H9 ASD Installation and Operation Manual

Page 160
Image 160
Toshiba H9 operation manual F402 F409, Motor Rated Capacity, Motor Rated Current, Motor Rated RPM