F205 | F205 |
V/I Input Point 1 Rate
Program ⇒ Torque ⇒ Setpoints
This parameter is used to set the gain and bias of the isolated V/I input terminal when the V/I terminal is used as the control input while operating in the Torque Control mode.
V/I Input Torque Control Setup
Perform the following setup to allow the system to receive Torque Control input at the V/I input terminal:
•Set SW301 of the Terminal Board to Voltage or Current (see Figure 9 on pg. 24).
•Program ⇒ Frequency ⇒ V/I Settings ⇒ V/I Voltage or Current input signal.
•Program ⇒ Fundamental ⇒ Standard Mode Selection ⇒ Frequency Mode 1
⇒ V/I.
•Program ⇒ Fundamental ⇒ Standard Mode Selection ⇒ Command Mode Selection ⇒ Terminal Block.
Torque Control
Perform the following setup to allow the system to perform Torque Control from the V/I input terminal:
•Set V/I Input Point 1 Rate (F205).
•Set V/I Input Point 1 Setting (F201) — the input analog signal level that corresponds to the torque setting at V/I Input Point 1 Rate.
•Set V/I Input Point 2 Rate (F206).
•Set V/I Input Point 2 Setting (F203) — the input analog signal level that corresponds to the torque setting at V/I Input Point 2 Rate.
•Provide a Run command (F and/or R).
Torque Control is accomplished by establishing an associated V/f output pattern for a given V/I input level.
Once set, as the V/I input voltage changes or the V/I current changes, the output torque of the ASD will vary in accordance with the above settings.
This parameter sets V/I Input Point 1 Rate and is the output torque value that is associated with the setting of V/I Input Point 1 Setting when operating in the Torque Control mode.
This value is entered as 0% to 250% of the rated torque.
Note: When using the isolated V/I input terminal the IICC terminal must be used as the return (negative) connection.
Direct Access Number — F205
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Torque Settings
H9 ASD Installation and Operation Manual | 107 |