F218

 

F219

 

 

 

RX Input Point 2 Setting

Direct Access Number —

F218

Program Frequency Speed Reference Setpoints

Parameter Type — Numerical

This parameter is used to set the gain and bias of the RX input terminal when

Factory Default — +100

 

Changeable During Run — Yes

the RX terminal is used as the control input while operating in the Speed

 

 

Control mode or the Torque Control mode.

Minimum — -100.0

 

This parameter sets the RX input level that is associated with RX Input Point 2

Maximum — +100.0

 

Frequency when operating in the Speed control mode or is associated with the

Units — %

 

RX Input Point 2 Rate when operating in the Torque Control mode.

 

 

 

This value is entered as -100% to +100% of the RX input signal range.

 

 

See RX Input Point 1 Setting for more information on this setting when used

 

 

for Speed control.

 

 

See RX Input Point 1 Rate for more information on this setting when used for

 

 

Torque Control.

 

 

 

 

 

RX Input Point 2 Frequency

Direct Access Number —

F219

Program Frequency Speed Reference Setpoints

Parameter Type — Numerical

This parameter is used to set the gain and bias of the RX input terminal when

Factory Default — 60.00

 

Changeable During Run — Yes

the RX terminal is used as the control input while operating in the Speed

 

 

Control mode.

Minimum — 0.00.

 

This parameter sets RX Input Point 2 Frequency and is the frequency that is

Maximum — Max. Freq. (F011)

associated with the setting of RX Input Point 2 Setting when operating in the

Units — Hz

 

 

 

Speed Control mode.

See RX Input Point 1 Setting for more information on this setting.

114

H9 ASD Installation and Operation Manual

Page 122
Image 122
Toshiba H9 operation manual F218 F219, RX Input Point 2 Setting, RX Input Point 2 Frequency, Direct Access Number F218