Frequency Point Selection

Program Communications Communication Reference Adjust

This parameter is used to set the communications reference for scaling.

See F811 F814 for more information on this setting.

Note: Scaling the communications signal is not required for all applications.

Direct Access Number — F810

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — Yes

Changes made to this parameter require that the power be cycled (Off then On) for the changes to take effect.

Settings:

0 — Disabled

1 — RS485 (2-wire)

2 — RS485 (4-wire)

3 — Communication Card

Point 1 Setting

Direct Access Number —

F811

Program Communications Communication Reference Adjust

Parameter Type — Numerical

When enabled at F810, this parameter is used to allow the user to set the gain

Factory Default — 0

 

Changeable During Run — Yes

and bias of the speed control input to the drive when the speed control signal is

 

 

received via the source selected at F810.

Minimum — 0

 

Gain and Bias Settings

Maximum — 100

 

Units — %

 

When operating in the Speed Control mode and using one of the control

 

 

 

sources from Settings above, the settings that determine the gain and bias

 

 

properties of the input signal are:

 

 

Communications Reference Speed Setpoint #1 (frequency) (F812),

 

 

• the communications input signal value that represents Communications

 

 

Reference Speed Setpoint #1 (frequency): F811,

 

 

Communications Reference Speed Setpoint #2 (frequency) (F814), and

 

 

• the communications input signal value that represents Communications

 

 

Reference Speed Setpoint #2 (frequency): F813.

 

 

Once set, as the input signal value changes, the output frequency of the drive

 

 

will vary in accordance with the above settings.

 

 

This parameter sets the Communications Reference input value that represents

 

 

Communications Reference Speed Setpoint #1 (frequency). This value is

 

 

entered as 0 to 100% of the Communications Reference input value range.

 

 

Changes made to this parameter require that the power be cycled (Off then On)

 

 

for the changes to take effect.

 

 

Point 1 Frequency

Direct Access Number —

F812

Program Communications Communication Reference Adjust

Parameter Type — Numerical

 

Factory Default — 0.00

 

This parameter is used to set the gain and bias of the Communications

Reference speed control input.

Changeable During Run — Yes

See F811 for more information on this setting.

Minimum — 0.00

This parameter sets Communications Reference Speed Setpoint #1.

Maximum — Max. Freq. (F011)

Changes made to this parameter require that the power be cycled (Off then On) for the changes to take effect.

Units — Hz