Stall Prevention During Regeneration | Direct Access Number — | F453 | ||
Program ⇒ Protection ⇒ Stall | Parameter Type — Selection List | |||
This function of this parameter is to disable the Overvoltage Stall (F305) and | Factory Default — Enabled |
|
| |
Changeable During Run — Yes | ||||
the Overcurrent Stall (F017) function during regeneration only. | ||||
|
|
| ||
|
|
| ||
function during regeneration. |
|
|
| |
Settings: |
|
|
| |
0 — Disabled (Stall During Regenerative Braking) |
|
|
| |
1 — Enabled (No Stall During Regenerative Braking) |
|
|
| |
|
|
|
| |
Current Control Proportional Gain | Direct Access Number — | F458 | ||
Program ⇒ Feedback ⇒ PG Settings | Parameter Type — Numerical | |||
This parameter sets the sensitivity of the drive when monitoring the output | Factory Default — | |||
Changeable During Run — No | ||||
current to control speed. | ||||
|
|
| ||
The larger the value entered here, the more sensitive the drive is to changes in | Minimum — 0.0 |
|
| |
|
|
| ||
the received feedback. | Maximum — 100.0 |
|
| |
|
|
|
| |
Speed Loop Proportional Gain | Direct Access Number — | F460 | ||
Program ⇒ Feedback ⇒ PG Settings | Parameter Type — Numerical | |||
During | Factory Default — | |||
Changeable During Run — No | ||||
drive when monitoring the output speed for control. | ||||
|
|
| ||
The larger the value entered here, the larger the change in the output speed for a | Minimum — 1 |
|
| |
|
|
| ||
given received feedback signal. | Maximum — 9999 |
|
| |
|
|
|
| |
Speed Loop Stabilization Coefficient | Direct Access Number — | F461 | ||
Program ⇒ Feedback ⇒ PG Settings | Parameter Type — Numerical | |||
During | Factory Default — 100 |
|
| |
Changeable During Run — Yes | ||||
drive when monitoring the output speed for control. | ||||
|
|
| ||
The larger the value entered here, the quicker the response to changes in the | Minimum — 1 |
|
| |
|
|
| ||
received feedback. | Maximum — 9999 |
|
| |
|
|
|
| |
Load Moment of Inertia 1 | Direct Access Number — | F462 | ||
Program ⇒ Feedback ⇒ PG Settings | Parameter Type — Numerical | |||
This parameter is used for calculating accel/decel torque when compensating | Factory Default — 35 |
|
| |
Changeable During Run — Yes | ||||
for load inertia while operating in the Drooping Control mode. | ||||
|
|
| ||
| Minimum — 0 |
|
| |
| Maximum — 100 |
|
| |
|
|
|
| |
Second Speed Loop Proportional Gain | Direct Access Number — | F463 | ||
Program ⇒ Feedback ⇒ PG Settings | Parameter Type — Numerical | |||
During | Factory Default — | |||
Changeable During Run — No | ||||
when monitoring the output speed for control. | ||||
|
|
| ||
The larger the value entered here, the more sensitive the drive is to changes in | Minimum — 1 |
|
| |
|
|
| ||
the received feedback. | Maximum — 9999 |
|
|
160 | H9 ASD Installation and Operation Manual |