Toshiba H9 operation manual F453 F463

Models: H9

1 289
Download 289 pages 12.38 Kb
Page 168
Image 168

F453

 

F463

 

 

 

 

Stall Prevention During Regeneration

Direct Access Number —

F453

Program Protection Stall

Parameter Type — Selection List

This function of this parameter is to disable the Overvoltage Stall (F305) and

Factory Default — Enabled

 

 

Changeable During Run — Yes

the Overcurrent Stall (F017) function during regeneration only.

 

 

 

Application-specific conditions may occur that warrant disabling the Stall

 

 

 

function during regeneration.

 

 

 

Settings:

 

 

 

0 — Disabled (Stall During Regenerative Braking)

 

 

 

1 — Enabled (No Stall During Regenerative Braking)

 

 

 

 

 

 

 

Current Control Proportional Gain

Direct Access Number —

F458

Program Feedback PG Settings

Parameter Type — Numerical

This parameter sets the sensitivity of the drive when monitoring the output

Factory Default — (ASD-dependent)

Changeable During Run — No

current to control speed.

 

 

 

The larger the value entered here, the more sensitive the drive is to changes in

Minimum — 0.0

 

 

 

 

 

the received feedback.

Maximum — 100.0

 

 

 

 

 

 

Speed Loop Proportional Gain

Direct Access Number —

F460

Program Feedback PG Settings

Parameter Type — Numerical

During closed-loop operation, this parameter sets the response sensitivity of the

Factory Default — (ASD-dependent)

Changeable During Run — No

drive when monitoring the output speed for control.

 

 

 

The larger the value entered here, the larger the change in the output speed for a

Minimum — 1

 

 

 

 

 

given received feedback signal.

Maximum — 9999

 

 

 

 

 

 

Speed Loop Stabilization Coefficient

Direct Access Number —

F461

Program Feedback PG Settings

Parameter Type — Numerical

During closed-loop operation, this parameter sets the response sensitivity of the

Factory Default — 100

 

 

Changeable During Run — Yes

drive when monitoring the output speed for control.

 

 

 

The larger the value entered here, the quicker the response to changes in the

Minimum — 1

 

 

 

 

 

received feedback.

Maximum — 9999

 

 

 

 

 

 

Load Moment of Inertia 1

Direct Access Number —

F462

Program Feedback PG Settings

Parameter Type — Numerical

This parameter is used for calculating accel/decel torque when compensating

Factory Default — 35

 

 

Changeable During Run — Yes

for load inertia while operating in the Drooping Control mode.

 

 

 

 

Minimum — 0

 

 

 

Maximum — 100

 

 

 

 

 

 

Second Speed Loop Proportional Gain

Direct Access Number —

F463

Program Feedback PG Settings

Parameter Type — Numerical

During closed-loop operation, this parameter sets the sensitivity of the drive

Factory Default — (ASD-dependent)

Changeable During Run — No

when monitoring the output speed for control.

 

 

 

The larger the value entered here, the more sensitive the drive is to changes in

Minimum — 1

 

 

 

 

 

the received feedback.

Maximum — 9999

 

 

160

H9 ASD Installation and Operation Manual

Page 168
Image 168
Toshiba H9 operation manual F453 F463