F464 |
| F471 | ||
|
|
|
| |
Second Speed Loop Stabilization Coefficient | Direct Access Number — | F464 | ||
Program ⇒ Feedback ⇒ PG Settings | Parameter Type — Numerical | |||
During | Factory Default — 1 |
|
| |
Changeable During Run — Yes | ||||
drive when monitoring the output speed for control. | ||||
|
|
| ||
The larger the value entered here, the quicker the response to changes in the | Minimum — 1 |
|
| |
|
|
| ||
received feedback. | Maximum — 9999 |
|
| |
|
|
|
| |
Load Moment of Inertia 2 | Direct Access Number — | F465 | ||
Program ⇒ Feedback ⇒ PG Settings | Parameter Type — Numerical | |||
This parameter is used for calculating accel/decel torque when compensating | Factory Default — 35 |
|
| |
Changeable During Run — Yes | ||||
for load inertia while operating in the Drooping Control mode. | ||||
|
|
| ||
| Minimum — 0 |
|
| |
| Maximum — 100 |
|
| |
|
|
|
| |
Speed PID Switching Frequency | Direct Access Number — | F466 | ||
Program ⇒ Feedback ⇒ Feedback Settings | Parameter Type — Numerical | |||
| Factory Default — 0.00 |
|
|
While running, this parameter establishes the threshold speed setting that is
used to determine if PID control may engage or remain engaged if active.
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
V/I Input Bias
Program ⇒ Frequency ⇒ Speed Reference Setpoints
This parameter is used to
Note: See note on pg. 43 for more information on the V/I terminal.
This setting may be used to ensure that the zero level of the input source (pot, pressure transducer, flow meter, etc.) is also the zero level setting of the ASD system.
This is accomplished by setting the input source to zero and adjusting this setting to provide an output of zero from the ASD.
Direct Access Number — F470
Parameter Type — Numerical
Factory Default — 127
Changeable During Run — Yes
Minimum — 0
Maximum — 255
V/I Input Gain
Program ⇒ Frequency ⇒ Speed Reference Setpoints
This parameter is used to fine tune the gain of the V/I input terminals.
Note: See note on pg. 43 for more information on the V/I terminal.
This setting may be used to ensure that the 100% level of the input source (pot, pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD system.
This is accomplished by setting the input source to 100% and adjusting this setting to provide an output of 100% from the ASD.
Direct Access Number — F471
Parameter Type — Numerical
Factory Default — 129
Changeable During Run — Yes
Minimum — 0
Maximum — 255
H9 ASD Installation and Operation Manual | 161 |