F464

 

F471

 

 

 

 

Second Speed Loop Stabilization Coefficient

Direct Access Number —

F464

Program Feedback PG Settings

Parameter Type — Numerical

During closed-loop operation, this parameter sets the response sensitivity of the

Factory Default — 1

 

 

Changeable During Run — Yes

drive when monitoring the output speed for control.

 

 

 

The larger the value entered here, the quicker the response to changes in the

Minimum — 1

 

 

 

 

 

received feedback.

Maximum — 9999

 

 

 

 

 

 

Load Moment of Inertia 2

Direct Access Number —

F465

Program Feedback PG Settings

Parameter Type — Numerical

This parameter is used for calculating accel/decel torque when compensating

Factory Default — 35

 

 

Changeable During Run — Yes

for load inertia while operating in the Drooping Control mode.

 

 

 

 

Minimum — 0

 

 

 

Maximum — 100

 

 

 

 

 

 

Speed PID Switching Frequency

Direct Access Number —

F466

Program Feedback Feedback Settings

Parameter Type — Numerical

 

Factory Default — 0.00

 

 

While running, this parameter establishes the threshold speed setting that is

used to determine if PID control may engage or remain engaged if active.

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (F011)

Units — Hz

V/I Input Bias

Program Frequency Speed Reference Setpoints

This parameter is used to fine-tune the bias of the V/I input terminals.

Note: See note on pg. 43 for more information on the V/I terminal.

This setting may be used to ensure that the zero level of the input source (pot, pressure transducer, flow meter, etc.) is also the zero level setting of the ASD system.

This is accomplished by setting the input source to zero and adjusting this setting to provide an output of zero from the ASD.

Direct Access Number — F470

Parameter Type — Numerical

Factory Default — 127

Changeable During Run — Yes

Minimum — 0

Maximum — 255

V/I Input Gain

Program Frequency Speed Reference Setpoints

This parameter is used to fine tune the gain of the V/I input terminals.

Note: See note on pg. 43 for more information on the V/I terminal.

This setting may be used to ensure that the 100% level of the input source (pot, pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD system.

This is accomplished by setting the input source to 100% and adjusting this setting to provide an output of 100% from the ASD.

Direct Access Number — F471

Parameter Type — Numerical

Factory Default — 129

Changeable During Run — Yes

Minimum — 0

Maximum — 255

H9 ASD Installation and Operation Manual

161

Page 169
Image 169