Table 11. My Function Operator selections.

My Function Computational Selections

Input

 

 

 

 

 

 

Function

Function Name

 

 

 

 

Function Description

Command

 

 

 

 

 

 

 

 

 

0

NOP (No Operation)

Disables the My Function feature.

 

 

 

1

ST

Execute data read/transfer.

 

 

 

2

STN

Execute inverted data read/transfer.

 

 

 

3

AND

Logical product of A AND B.

 

 

 

 

 

4

ANDN

Logical product of A AND

 

 

B.

 

 

 

5

OR

Logical sum of A OR B.

 

 

 

6

ORN

Logical sum of A OR

 

 

 

 

B.

 

 

 

7

EQ

Compares data — Outputs 1 if Equal; 0 if not Equal.

 

 

 

8

NE

Compares data — Outputs 0 if Equal; 1 if not Equal.

 

 

 

9

GT

Compares data — Outputs 1 if A>B; 0 if AB.

 

 

 

10

GE

Compares data — Outputs 1 if AB; 0 if A<B.

 

 

 

11

LT

Compares data — Outputs 1 if A<B; 0 if AB.

 

 

 

12

LE

Compares data — Outputs 1 if AB; 0 if A>B.

 

 

 

13

ASUB

Outputs absolute difference between A and B — A–B

 

 

 

14

ON (Timer)

Enables the On response time delay settings of My Function Time Data 1 5

(F928 F932) for My Function Data.

 

 

 

 

 

15

OFF (Timer)

Enables the Off response time delay settings of My Function Time Data 1 5

(F928 F932) for My Function Data.

 

 

 

 

 

16

COUNT1 (Timer)

Outputs a 1 upon reaching the pulse count setting of F933.

 

 

 

17

COUNT2 (Timer)

Outputs a 1 upon reaching the pulse count setting of F934.

 

 

 

18

HOLD

Outputs the peak output value since powering up or since the last reset.

 

 

 

19

SET

Sets data.

 

 

 

20

RESET

Resets data.

 

 

 

 

 

 

 

H9 ASD Installation and Operation Manual

245

Page 253
Image 253
Toshiba H9 operation manual My Function Operator selections, F928 F932 for My Function Data