Low Current Detection Threshold
Program ⇒ Protection ⇒ Low Current Settings
With the
The threshold value is entered as a percentage of the maximum rating of the drive.
Direct Access Number — F611
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
Low Current Trip Threshold Time
Program ⇒ Protection ⇒ Low Current Settings
With the
Direct Access Number — F612
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 255
Units — Seconds
Short Circuit Detection At Start
Program ⇒ Protection ⇒ Special Protection Parameters
This parameter determines when the system will perform an Output Short Circuit test.
Note: Selection 3 is recommended for
Settings:
0 — Every Start (standard pulse)
1 — Power On or Reset (standard pulse)
2 — Every Start (short pulse)
3 — Power On or Reset (short pulse)
Direct Access Number — F613
Parameter Type — Selection List
Factory Default — Every Start (standard pulse)
Changeable During Run — No
Overtorque Trip
Program ⇒ Protection ⇒ Overtorque Parameters
This parameter Enables/Disables the Overtorque Tripping function.
When enabled, the ASD trips if an output torque value greater than the setting of F616 or F617 exists for a time longer than the setting of F618.
When disabled, the ASD does not trip due to overtorque conditions.
Direct Access Number — F615
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Note: A discrete output terminal may be activated when an overtorque alarm occurs if so configured (see F130).
Settings:
0 — Disabled
1 — Enabled
H9 ASD Installation and Operation Manual | 185 |