F472

F475

RR Input Bias

Program Frequency Speed Reference Setpoints

This parameter is used to fine tune the bias of the RR input terminal when this terminal is used as the control input while operating in the Speed Control mode or the Torque Control mode.

This setting may be used to ensure that the zero level of the input source (pot, pressure transducer, flow meter, etc.) is also the zero level setting of the ASD system.

This is accomplished by setting the input source to zero and adjusting this setting to provide an output of zero from the ASD.

Direct Access Number — F472

Parameter Type — Numerical

Factory Default — 128

Changeable During Run — Yes

Minimum — 0

Maximum — 255

RR Input Gain

Program Frequency Speed Reference Setpoints

This parameter is used to fine tune the gain of the RR input terminal when this terminal is used as the control input while operating in the Speed Control mode or the Torque Control mode.

This setting may be used to ensure that the 100% level of the input source (pot, pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD system.

This is accomplished by setting the input source to 100% and adjusting this setting to provide an output of 100% from the ASD.

Direct Access Number — F473

Parameter Type — Numerical

Factory Default — 154

Changeable During Run — Yes

Minimum — 0

Maximum — 255

RX Input Bias

Direct Access Number —

F474

Program Frequency Speed Reference Setpoints

Parameter Type — Numerical

This parameter is used to fine tune the bias of the RX input terminal when this

Factory Default — 127

 

Changeable During Run — Yes

terminal is used as the control input while operating in the Speed Control

 

 

mode or the Torque Control mode.

Minimum — 0

 

This setting may be used to ensure that the zero level of the input source (pot,

Maximum — 255

 

pressure transducer, flow meter, etc.) is also the zero level setting of the ASD

 

 

system.

 

 

This is accomplished by setting the input source to zero and adjusting this

 

 

setting to provide an output of zero from the ASD.

 

 

 

 

 

RX Input Gain

Direct Access Number —

F475

Program Frequency Speed Reference Setpoints

Parameter Type — Numerical

This parameter is used to fine tune the gain of the RX input terminal when this

Factory Default — 127

 

Changeable During Run — Yes

terminal is used as the control input while operating in the Speed Control

 

 

mode or the Torque Control mode.

Minimum — 0

 

This setting may be used to ensure that the 100% level of the input source (pot,

Maximum — 255

 

pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD

 

 

system.

 

 

This is accomplished by setting the input source to 100% and adjusting this setting to provide an output of 100% from the ASD.

162

H9 ASD Installation and Operation Manual

Page 170
Image 170
Toshiba H9 operation manual F472 F475, RR Input Bias, RR Input Gain, RX Input Bias, RX Input Gain