F427 |
| F431 | ||
|
|
| ||
Reverse Speed Limit Input | Direct Access Number — | F427 | ||
Program ⇒ Torque ⇒ Torque Control | Parameter Type — Selection List | |||
This parameter Enables/Disables the Reverse Speed Limit Input control | Factory Default — Disabled |
| ||
Changeable During Run — Yes | ||||
function. When enabled and operating in the Torque Control mode, the reverse | ||||
|
| |||
speed limit is controlled by the terminal selected here. If Setting is selected, the |
|
| ||
value set at F428 is used as the Reverse Speed Limit input. |
|
| ||
Settings: |
|
| ||
0 | — Disabled |
|
| |
1 | — V/I |
|
| |
2 | — RR |
|
| |
3 | — RX |
|
| |
4 | — Setting (F428) |
|
| |
|
|
| ||
Reverse Speed Limit Input Level | Direct Access Number — | F428 | ||
Program ⇒ Torque ⇒ Torque Control | Parameter Type — Numerical | |||
This parameter provides a value to be used as the Reverse Speed Limit setting | Factory Default — 80.0 |
| ||
Changeable During Run — Yes | ||||
if Setting is selected at F427. | ||||
|
| |||
|
| Minimum — 0.00 |
| |
|
| Maximum — Upper Limit (F012) | ||
|
| Units — Hz |
| |
|
|
| ||
Speed Limit (torque=0) Center Value Reference | Direct Access Number — | F430 | ||
Program ⇒ Torque ⇒ Torque Speed Limiting | Parameter Type — Selection List | |||
The system has the ability to limit the amount that the speed may vary as a | Factory Default — Disabled |
| ||
Changeable During Run — Yes | ||||
function of a changing load while operating in the Torque Control mode. This | ||||
|
| |||
parameter sets the input terminal that will be used to control the allowable |
|
| ||
speed variance. |
|
| ||
Settings: |
|
| ||
0 | — Disabled |
|
| |
1 | — V/I |
|
| |
2 | — RR |
|
| |
3 | — RX |
|
| |
4 | — F431 Setting |
|
| |
|
|
| ||
Speed Limit (torque=0) Center Value | Direct Access Number — | F431 | ||
Program ⇒ Torque ⇒ Torque Speed Limiting | Parameter Type — Numerical | |||
The system has the ability to limit the amount that the speed may vary as a | Factory Default — 0.00 |
| ||
Changeable During Run — Yes | ||||
function of a changing load while operating in the Torque Control mode. This | ||||
|
| |||
parameter sets the targeted speed. The | Minimum — 0.00 |
| ||
setting may be set at F432. | Maximum — Max. Freq. (F011) | |||
|
|
Units — Hz
156 | H9 ASD Installation and Operation Manual |