F427

 

F431

 

 

 

Reverse Speed Limit Input

Direct Access Number —

F427

Program Torque Torque Control

Parameter Type — Selection List

This parameter Enables/Disables the Reverse Speed Limit Input control

Factory Default — Disabled

 

Changeable During Run — Yes

function. When enabled and operating in the Torque Control mode, the reverse

 

 

speed limit is controlled by the terminal selected here. If Setting is selected, the

 

 

value set at F428 is used as the Reverse Speed Limit input.

 

 

Settings:

 

 

0

— Disabled

 

 

1

— V/I

 

 

2

— RR

 

 

3

— RX

 

 

4

— Setting (F428)

 

 

 

 

 

Reverse Speed Limit Input Level

Direct Access Number —

F428

Program Torque Torque Control

Parameter Type — Numerical

This parameter provides a value to be used as the Reverse Speed Limit setting

Factory Default — 80.0

 

Changeable During Run — Yes

if Setting is selected at F427.

 

 

 

 

Minimum — 0.00

 

 

 

Maximum — Upper Limit (F012)

 

 

Units — Hz

 

 

 

 

Speed Limit (torque=0) Center Value Reference

Direct Access Number —

F430

Program Torque Torque Speed Limiting

Parameter Type — Selection List

The system has the ability to limit the amount that the speed may vary as a

Factory Default — Disabled

 

Changeable During Run — Yes

function of a changing load while operating in the Torque Control mode. This

 

 

parameter sets the input terminal that will be used to control the allowable

 

 

speed variance.

 

 

Settings:

 

 

0

— Disabled

 

 

1

— V/I

 

 

2

— RR

 

 

3

— RX

 

 

4

F431 Setting

 

 

 

 

 

Speed Limit (torque=0) Center Value

Direct Access Number —

F431

Program Torque Torque Speed Limiting

Parameter Type — Numerical

The system has the ability to limit the amount that the speed may vary as a

Factory Default — 0.00

 

Changeable During Run — Yes

function of a changing load while operating in the Torque Control mode. This

 

 

parameter sets the targeted speed. The plus-or-minus value (range) for this

Minimum — 0.00

 

setting may be set at F432.

Maximum — Max. Freq. (F011)

 

 

Units — Hz