232 H9 ASD Installation and Operation Manual

Virtual Input Terminal 1 Selection

Program Terminal Input Terminals
This parameter is used to set the functionality of the Virtual Input Terminal 1.
As a virtual terminal, i t exists only in memory a nd is considered to always be in
its True (connected to CC) state.
It is often practical to assign a function t o this terminal that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets th e programmable Virtual Input Terminal 1 terminal to
one of the functions that are listed in Table 5 on pg. 236.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
Direct Access Number — F973
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No

Virtual Input Terminal 2 Selection

Program Terminal Input Terminals
This parameter is used to set the functionality of the Virtual Input Terminal 2.
As a virtual terminal, i t exists only in memory a nd is considered to always be in
its True (connected to CC) state.
It is often practical to assign a function t o this terminal that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets th e programmable Virtual Input Terminal 2 terminal to
one of the functions that are listed in Table 5 on pg. 236.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
Direct Access Number — F974
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No

Virtual Input Terminal 3 Selection

Program Terminal Input Terminals
This parameter is used to set the functionality of the Virtual Input Terminal 3.
As a virtual terminal, i t exists only in memory a nd is considered to always be in
its True (connected to CC) state.
It is often practical to assign a function t o this terminal that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets th e programmable Virtual Input Terminal 3 terminal to
one of the functions that are listed in Table 5 on pg. 236.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
Direct Access Number — F975
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No

Virtual Input Terminal 4 Selection

Program Terminal Input Terminals
This parameter is used to set the functionality of the Virtual Input Terminal 4.
As a virtual terminal, i t exists only in memory a nd is considered to always be in
its True (connected to CC) state.
It is often practical to assign a function t o this terminal that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets th e programmable Virtual Input Terminal 4 terminal to
one of the functions that are listed in Table 5 on pg. 236.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
Direct Access Number — F976
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
F973 F976