PTC2 Thermal Selection
Program ⇒ Special ⇒ Special Parameters⇒ PTC2 Thermal Selection
This parameter Enables/Disables the optional external thermal detection circuit of the Expansion IO Card Option 2. A thermistor is connected from TH1+ to TH1- of TB4 on the Expansion IO Card Option 2.
Should the thermistor resistance reading fall below 50Ω because of an over- temperature condition or exceed 3000Ω because of an open circuit an External Thermal Fault (OH2) will be incurred.
Direct Access Number — F638
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Note: While this parameter is Enabled, the system cannot be restarted until the thermistor value recovers to the level of 1.8kΩ from an
Settings:
0 — Disabled
1 — Detect Disconnect
Braking Resistance Overload Time (10x rated torque) | Direct Access Number — F639 | |
Program ⇒ Protection ⇒ Dynamic Braking | Parameter Type — Numerical | |
This parameter sets the time that the braking resistor is allowed to sustain and | Factory Default — 5.0 | |
Changeable During Run — No | ||
overload condition before a trip is incurred. | ||
| ||
This feature is useful for applications that have a fluctuating load or for loads | Minimum — 0.1 | |
Maximum — 600.0 | ||
that require a long deceleration time. | ||
| ||
| Units — Seconds |
Step-Out Current Detection Level
Program ⇒ Motor ⇒ PM Motor
This parameter is used with synchronous motor applications only.
Contact Toshiba Customer Service Department for information on this parameter.
Direct Access Number — F640
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 10
Maximum — 150
Units — %
Step-Out Current Detection Time
Program ⇒ Motor ⇒ PM Motor
This parameter is used with synchronous motor applications only.
Contact Toshiba Customer Service Department for information on this parameter.
Direct Access Number — F641
Parameter Type — Numerical
Factory Default — 00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 25.0
Units — Seconds
192 | H9 ASD Installation and Operation Manual |