F506 |
| F510 | |
|
|
| |
| Direct Access Number — | F506 | |
Program ⇒ Special ⇒ Accel/Decel Special | Parameter Type — Numerical | ||
During an | Factory Default — 10 |
| |
Changeable During Run — Yes | |||
acceleration rate for the lower part of the acceleration curve by the percentage | |||
|
| ||
set here. | Minimum — 0 |
| |
This function is commonly used with transportation and lifting applications. | Maximum — 50 |
| |
See parameter F502 on pg. 165 for more information on this setting. | Units — % |
| |
|
|
| |
| Direct Access Number — | F507 | |
Program ⇒ Special ⇒ Accel/Decel Special | Parameter Type — Numerical | ||
During an | Factory Default — 10 |
| |
Changeable During Run — Yes | |||
acceleration rate for the upper part of the acceleration curve by the percentage | |||
|
| ||
set here. | Minimum — 0 |
| |
This function is commonly used with transportation and lifting applications. | Maximum — 50 |
| |
See parameter F502 on pg. 165 for more information on this setting. | Units — % |
| |
|
|
| |
| Direct Access Number — | F508 | |
Program ⇒ Special ⇒ Accel/Decel Special | Parameter Type — Numerical | ||
During an | Factory Default — 10 |
| |
Changeable During Run — Yes | |||
deceleration rate for the lower part of the deceleration curve by the percentage | |||
|
| ||
set here. | Minimum — 0 |
| |
This function is commonly used with transportation and lifting applications. | Maximum — 50 |
| |
See parameter F502 on pg. 165 for more information on this setting. | Units — % |
| |
|
|
| |
| Direct Access Number — | F509 | |
Program ⇒ Special ⇒ Accel/Decel Special | Parameter Type — Numerical | ||
During an | Factory Default — 10 |
| |
Changeable During Run — Yes | |||
deceleration rate for the upper part of the deceleration curve by the percentage | |||
|
| ||
set here. | Minimum — 0 |
| |
This function is commonly used with transportation and lifting applications. | Maximum — 50 |
| |
See parameter F502 on pg. 165 for more information on this setting. | Units — % |
| |
|
|
| |
Acceleration Time 3 | Direct Access Number — | F510 | |
Program ⇒ Special ⇒ Accel/Decel #1 – #4 Settings | Parameter Type — Numerical | ||
This parameter specifies the time in seconds for the output of the ASD to go | Factory Default — | ||
Changeable During Run — Yes | |||
from 0.0 Hz to the Maximum Frequency for the #3 Acceleration profile. The | |||
|
| ||
Accel/Decel pattern may be set using F502. The minimum Accel/Decel time | Minimum — 0.1 |
| |
may be set using F508. | Maximum — 6000 |
| |
|
|
Note: | An acceleration time shorter than the load will allow may cause | Units — Seconds |
| nuisance tripping and mechanical stress to loads. Automatic | |
|
| |
| Accel/Decel, Stall, and Ridethrough settings may lengthen the |
|
| acceleration times. |
|
168 | H9 ASD Installation and Operation Manual |