F506

 

F510

 

 

 

S-Pattern Acceleration Lower Limit Adjustment

Direct Access Number —

F506

Program Special Accel/Decel Special

Parameter Type — Numerical

During an S-Pattern 1 or 2 sequence, this parameter settings modifies the

Factory Default — 10

 

Changeable During Run — Yes

acceleration rate for the lower part of the acceleration curve by the percentage

 

 

set here.

Minimum — 0

 

This function is commonly used with transportation and lifting applications.

Maximum — 50

 

See parameter F502 on pg. 165 for more information on this setting.

Units — %

 

 

 

 

S-Pattern Acceleration Upper Limit Adjustment

Direct Access Number —

F507

Program Special Accel/Decel Special

Parameter Type — Numerical

During an S-Pattern 1 or 2 sequence, this parameter settings modifies the

Factory Default — 10

 

Changeable During Run — Yes

acceleration rate for the upper part of the acceleration curve by the percentage

 

 

set here.

Minimum — 0

 

This function is commonly used with transportation and lifting applications.

Maximum — 50

 

See parameter F502 on pg. 165 for more information on this setting.

Units — %

 

 

 

 

S-Pattern Deceleration Lower Limit Adjustment

Direct Access Number —

F508

Program Special Accel/Decel Special

Parameter Type — Numerical

During an S-Pattern 1 or 2 sequence, this parameter settings modifies the

Factory Default — 10

 

Changeable During Run — Yes

deceleration rate for the lower part of the deceleration curve by the percentage

 

 

set here.

Minimum — 0

 

This function is commonly used with transportation and lifting applications.

Maximum — 50

 

See parameter F502 on pg. 165 for more information on this setting.

Units — %

 

 

 

 

S-Pattern Deceleration Upper Limit Adjustment

Direct Access Number —

F509

Program Special Accel/Decel Special

Parameter Type — Numerical

During an S-Pattern 1 or 2 sequence, this parameter settings modifies the

Factory Default — 10

 

Changeable During Run — Yes

deceleration rate for the upper part of the deceleration curve by the percentage

 

 

set here.

Minimum — 0

 

This function is commonly used with transportation and lifting applications.

Maximum — 50

 

See parameter F502 on pg. 165 for more information on this setting.

Units — %

 

 

 

 

Acceleration Time 3

Direct Access Number —

F510

Program Special Accel/Decel #1 – #4 Settings

Parameter Type — Numerical

This parameter specifies the time in seconds for the output of the ASD to go

Factory Default — (ASD-dependent)

Changeable During Run — Yes

from 0.0 Hz to the Maximum Frequency for the #3 Acceleration profile. The

 

 

Accel/Decel pattern may be set using F502. The minimum Accel/Decel time

Minimum — 0.1

 

may be set using F508.

Maximum — 6000

 

 

 

Note:

An acceleration time shorter than the load will allow may cause

Units — Seconds

 

nuisance tripping and mechanical stress to loads. Automatic

 

 

 

Accel/Decel, Stall, and Ridethrough settings may lengthen the

 

 

acceleration times.

 