168 H9 ASD Installation and Operation Manual

S-Pattern Acceleration Lower Limit Adjus t me nt

Program Special Accel/Decel Special
During an S-Pattern 1 or 2 sequence, this parameter settings modifies the
acceleration rate for the lower part of the acceleration curve by the percentage
set here.
This function is comm only used with transpo rtation and lifting ap plications.
See parameter F502 on pg. 165 for more information on this sett ing.
Direct Access Number — F506
Parameter Type — Numeri cal
Factory Default — 10
Changeable During Run — Yes
Minimum — 0
Maximum — 50
Units — %

S-Pattern Acceleration Upper Limit Adjustment

Program Special Accel/Decel Special
During an S-Pattern 1 or 2 sequence, this parameter settings modifies the
acceleration rate for the upper part of the acceleration curve by the percentage
set here.
This function is comm only used with transpo rtation and lifting ap plications.
See parameter F502 on pg. 165 for more information on this sett ing.
Direct Access Number — F507
Parameter Type — Numeri cal
Factory Default — 10
Changeable During Run — Yes
Minimum — 0
Maximum — 50
Units — %

S-Pattern Deceleration Lower Limit Adjus t me nt

Program Special Accel/Decel Special
During an S-Pattern 1 or 2 sequence, this parameter settings modifies the
deceleration rate for the lower part of the deceleration curve by the percentage
set here.
This function is comm only used with transpo rtation and lifting ap plications.
See parameter F502 on pg. 165 for more information on this sett ing.
Direct Access Number — F508
Parameter Type — Numeri cal
Factory Default — 10
Changeable During Run — Yes
Minimum — 0
Maximum — 50
Units — %

S-Pattern Deceleration Upper Limit Adjustment

Program Special Accel/Decel Special
During an S-Pattern 1 or 2 sequence, this parameter settings modifies the
deceleration rate for the upper part of the deceleration curve by the percentage
set here.
This function is comm only used with transpo rtation and lifting ap plications.
See parameter F502 on pg. 165 for more information on this sett ing.
Direct Access Number — F509
Parameter Type — Numeri cal
Factory Default — 10
Changeable During Run — Yes
Minimum — 0
Maximum — 50
Units — %

Acceleration Time 3

Program Special Accel/Decel #1 – #4 Settings
This parameter specif ies the time in secon ds for the output of the ASD to go
from 0.0 Hz to the Maximum Frequency for the #3 Acceleration profile. The
Accel/Decel pattern may be set using F502. The minimum Accel/Decel time
may be set using F508.
Note: An acceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads. Automatic
Accel/Decel, Stall, and Ridethrough settings may lengthen the
acceleration times.
Direct Access Number — F510
Parameter Type — Numeri cal
Factory Default — (ASD-dependent)
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
F506 F510