Short Circuit Protection Recommendations

Table 22. 230/240 and 400/480-Volt ASD recommended circuit breaker selection.

Model Number

HP

Continuous Output Current

Circuit Breaker Part Number

VT130H9U

(Amps)

 

 

 

 

 

 

 

 

 

 

2035

3.0

10.0

HLL36025

 

 

 

 

2055

5.0

17.5

HLL36025

 

 

 

 

2080

7.5

27.5

HLL36040

 

 

 

 

2110

10

33.0

HLL36050

 

 

 

 

2160

15

54.0

HLL36070

 

 

 

 

2220

20

66.0

HLL36090

 

 

 

 

2270

25

76.0

HLL36100

 

 

 

 

2330

30

90.0

HLL36100

 

 

 

 

2400

40

120

HLL36125

 

 

 

 

2500

50

152

HLL36150

 

 

 

 

2600

60

176

JLL36200

 

 

 

 

2750

75

221

 

 

 

 

 

210K

100

285

Contact Toshiba Customer Service

 

 

 

 

212K

125

365

 

 

 

 

 

4055

5

10.5

HLL36025

 

 

 

 

4080

7.5

14.3

HLL36040

 

 

 

 

4110

10

17.6

HLL36050

 

 

 

 

4160

15

27.7

HLL36070

 

 

 

 

4220

20

33.0

HLL36090

 

 

 

 

4270

25

41.0

HLL36100

 

 

 

 

4330

30

48.0

HLL36100

 

 

 

 

4400

40

66.0

HLL36125

 

 

 

 

4500

50

79.0

HLL36150

 

 

 

 

4600

60

94.0

JLL36200

 

 

 

 

4750

75

116

JLL36225

 

 

 

 

410K

100

160

JLL36250

 

 

 

 

412K

125

179

LIL36300

 

 

 

 

415K

150

215

LIL36300

 

 

 

 

420K

200

259

LIL36400

 

 

 

 

425K

250

314

LIL36400

 

 

 

 

430K

300

387

 

 

 

 

Contact Toshiba Customer Service

435K

350

434

 

 

 

 

440K

400

495

 

 

 

 

 

H9 ASD Installation and Operation Manual

267

Page 275
Image 275
Toshiba H9 operation manual Short Circuit Protection Recommendations