F106

F107

Input Terminal Priority

Program Terminal Input Special Functions

This parameter is used to allow the Jog and DC Injection Braking input signals to control the ASD when received via the Terminal Board even though the system is in the Local mode.

With this parameter enabled, a Jog command or a DC Injection Braking command received from the Terminal Board will receive priority over commands from the EOI.

Direct Access Number — F106

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No

See F260 for more information on using the Jog function.

See F250 F252 for more information on DC Injection Braking.

Settings:

0 — Disabled

1 — Enabled

16-Bit Binary/BCD Input

Program Terminal Input Special Functions

The extended terminal function is used with the optional Expansion IO Card Option (P/N ETB004Z).

This parameter defines the format of the binary or BCD data when using the option card.

Direct Access Number — F107

Parameter Type — Selection List

Factory Default — None

Changeable During Run — No

Note: The Expansion IO Card Option 2 option board is required to use this terminal.

See the Expansion IO Card Option 1 instruction manual (P/N 58685) for more information on the function of this terminal.

Settings:

0 — None

112-Bit Binary

216-Bit Binary

33-Digit BCD

44-Digit BCD

5— Inverted 12-Bit Binary

6— Inverted 16-Bit Binary

7— Inverted 3-Digit BCD

8— Inverted 4-Digit BCD

Selections using 16-bit binary or 4-digit BCD will require the configuration of terminals S1-S4 on the Terminal Board as binary bits 0 – 3 (F115 F118). The Frequency Mode 1 (F004) parameter must be set to Binary/BCD.

For proper scaling of the binary or BCD input, parameters F228 F231 must be configured.

H9 ASD Installation and Operation Manual

87

Page 95
Image 95
Toshiba H9 F106 F107, Input Terminal Priority, Bit Binary/BCD Input, Direct Access Number F106, Direct Access Number F107