F222

F222

RX2 (AI1) Input Point 1 Setting

Program Frequency Speed Reference Setpoints

This parameter is used to set the gain and bias of the RX2 (AI1) input terminal when the RX2 (AI1) terminal is used as the control input while operating in the Speed Control mode or the Torque Control mode.

Note: The Expansion IO Card Option 1 option board (P/N ETB003Z) is required to use this terminal.

This parameter sets the RX2 (AI1) input level that is associated with RX2 (AI1) Input Point 1 Frequency when operating in the Speed Control mode or is associated with the RX2 (AI1) Input Point 1 Rate when operating in the

Torque Control mode.

RX2 (AI1) Input Speed Control Setup

Perform the following setup to allow the system to receive Speed control input at the RX2 (AI1) input terminal:

Program Fundamental Standard Mode Selection Frequency Mode 1 RX2.

Program Fundamental Standard Mode Selection Command Mode Selection Terminal Block.

Speed Control

Perform the following setup to allow the system to perform Speed control from the RX2 (AI1) input terminal:

Set RX2 (AI1) Input Point 1 Frequency (F223).

Set RX2 (AI1) Input Point 1 Setting (F222) — the input analog signal level that corresponds to the speed setting at RX2 (AI1) Input Point 1 Frequency.

Set RX2 (AI1) Input Point 2 Frequency (F225).

Set RX2 (AI1) Input Point 2 Setting (F224) — the input analog signal level that corresponds to the speed setting at RX Input Point 2 Frequency.

Provide a Run command (F and/or R).

Once set, as the RX2 (AI1) input voltage changes, the ASD output speed and/or torque will vary in accordance with the above settings.

This parameter value is entered as -100% to +100% of the RX2 (AI1) input signal range.

See the Expansion IO Card Option 1 instruction manual (P/N 58685) for more information on the function of this terminal. And see parameter F476 and F477 for information on fine-tuning this terminal response.

Direct Access Number — F222

Parameter Type — Numerical

Factory Default — 0

Changeable During Run — Yes

Minimum — -100

Maximum — +100

Units — %

Frequency Settings

116

H9 ASD Installation and Operation Manual

Page 124