Emergency Off Mode Settings

Program Protection Emergency Off Settings

This parameter determines the method used to stop the motor in the event that an Emergency Off command is received and the system is configured to use this feature.

This setting may also be associated with the FL terminals to allow the FL relay to change states when an EOFF condition occurs by setting the FL terminal to Fault FL (all) (see F132).

Direct Access Number — F603

Parameter Type — Selection List

Factory Default — Coast Stop

Changeable During Run — No

Note: A supplemental emergency stopping system should be used with the ASD. Emergency stopping should not be a task of the ASD alone.

Settings:

0 — Coast Stop

1 — Deceleration Stop

2 — DC Injection Braking Stop

3 — Deceleration Stop (Decel #4 setting; F515)

Emergency Off DC Injection Application Time

Direct Access Number — F604

Program Protection Emergency Off Settings

Parameter Type — Numerical

When DC Injection is selected at F603 this parameter determines the time that

Factory Default — 1.0

Changeable During Run — Yes

the DC Injection braking is applied to the motor.

 

 

Minimum — 0.0

 

Maximum — 20.0

 

Units — Seconds

ASD Output Phase Failure Detection

Program Protection Phase Loss

This parameter Enables/Disables the monitoring of each phase of the 3-phase output signal (U, V, or W) of the ASD. If either line is missing, inactive, or not of the specified level for one second or more, the ASD incurs a trip.

Direct Access Number — F605

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No

Note: Autotune checks for phase failures regardless of this setting.

Settings:

0 — Disabled (no detection)

1 — Enabled (Run at Startup and Retry)

2 — Enabled (every Run command and Retry)

3 — Enabled (during Run)

4 — Enabled (at Startup and during Run)

5 — Enabled (detects an ALL-PHASE failure ONLY - will not trip, restarts at reconnect)

H9 ASD Installation and Operation Manual

183

Page 191
Image 191
Toshiba H9 operation manual F603 F605, Emergency Off Mode Settings, Emergency Off DC Injection Application Time