DCA-10SPX3 — LOAD APPLICATION

DCA-10SPX3 — LOAD APPLICATION

Single Phase, Load

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage and frequency requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130— 150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.

NOTE

If wattage is not given on the equipment's name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 1.0. See Table 10. below when connecting loads.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable.

When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

When connecting a fluorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

Table 10. Power Factor By Load

Type Of Load

Power Factor

 

 

Single-phase induction motors

0.4 - 0.75

 

 

Electric heaters, incandescent

1.0

lamps

 

 

 

Fluorescent lamps, mercury lamps

0.4 - 0.9

 

 

Electronic devices, communication

1.0

equipment

 

 

 

CAUTION:

Motors and motor-driven equipment draw much greater current for starting than during operation.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

PAGE 34 — DCA-10SPX3 A.C. GENERATOR— PARTS & OPERATION MANUAL — REV. #2 (01/17/11)