PID Deviation Lower Limit
Program ⇒ Feedback ⇒ Feedback Settings
This parameter determines the maximum amount that the feedback may decrease the output signal.
Direct Access Number — F365
Parameter Type — Numerical
Factory Default — 60.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 60.00
Units — Hz
PID Feedback Differential (D) Gain
Program ⇒ Feedback ⇒ Feedback Settings
This parameter determines the degree that the Differential function affects the output signal. The larger the value entered here, the more pronounced the affect of the differential function for a given feedback signal level.
Direct Access Number — F366
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.55
Process Upper Limit
Program ⇒ Feedback ⇒ Feedback Settings
Selecting Process PID at parameter F359 allows for this parameter setting to function as the Upper Limit while operating in the PID Control mode.
Direct Access Number — F367
Parameter Type — Numerical
Factory Default — 60.00
Changeable During Run — No
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Process Lower Limit
Program ⇒ Feedback ⇒ Feedback Settings
Selecting Process PID at parameter F359 allows for this parameter setting to function as the Lower Limit while operating in the PID Control mode.
Direct Access Number — F368
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
PID Control Wait Time | Direct Access Number — | F369 | |
Program ⇒ Feedback ⇒ Feedback Settings | Parameter Type — Numerical | ||
This parameter is used to delay the start of PID control at start up. During the | Factory Default — 0 |
| |
Changeable During Run — Yes | |||
wait time set here, the ASD will follow the frequency control input of the | |||
|
| ||
process value and the feedback input will be ignored until this setting times out. | Minimum — 0 |
| |
At which time the PID setup assumes control. | Maximum — 2400 |
| |
|
| ||
| Units — Seconds |
| |
|
|
| |
PID Output Upper Limit | Direct Access Number — | F370 | |
Program ⇒ Feedback ⇒ Feedback Settings | Parameter Type — Numerical | ||
| Factory Default — 60.00 |
|
Selecting Speed PID at parameter F359 allows for this parameter setting to
function as the Upper Limit while operating in the PID Control mode.
Changeable During Run — No
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
H9 ASD Installation and Operation Manual | 149 |