F740

F742

Trace Selection

Program Utilities Trace

In conjunction with parameter F741 F745, this parameter is used to monitor and store 4 ASD output waveform data points. The data may be read and stored as a function of a trip (At Trip) or it may be initiated by the activation of a discrete terminal activation (At Trigger). Set a discrete input terminal to Trace Back Trigger Signal and activate the terminal to initiate the At Trigger read/ store function.

Table 9 on pg. 242 lists the items that may be selected for the data read/store function along with the associated communication number for each selection.

The duration of the read/store cycle for the selected items is set at parameter F741.

To acquire and store the data a communications device and a PC are required. The H9 ASD supports the following communications protocols: RS485 (MODBUS-RTU) Toshiba Protocol, USB Toshiba Protocol, CC-Link, ProfiBus, and DeviceNet (Refer to the manual of each protocol type for more information).

Direct Access Number — F740

Parameter Type — Selection List

Factory Default — At Trip

Changeable During Run — Yes

Trace data may be viewed graphically via Program Utilities View Trace

Data.

Settings:

0 — None (disabled)

1 — At Trip

2 — At Trigger

Trace Cycle

Direct Access Number — F741

Program Utilities Trace

Parameter Type — Selection List

This parameter sets the record time for the Trace Data events selected at F742

Factory Default — 100 mS

Changeable During Run — Yes

F745.

 

See F740 for more information on this parameter setting.

 

Settings:

0 — 4 mS

1 — 20 mS

2 — 100 mS

3 — 1 Second

4 — 10 Seconds

Trace Data 1

Direct Access Number — F742

Program Utilities Trace

Parameter Type — Selection List

This parameter is used to select the Trace Data 1 item from Table 9 on pg. 242

Factory Default — Output Frequency

Changeable During Run — Yes

to be read and stored in accordance with the setup of parameters F740 and

 

F741.

 

See F740 for more information on this parameter setting.

 