96 H9 ASD Installation and Operation Manual

Input Terminal 4 (RES) Response Time

Program Termi nal Input Terminal Delays
This parameter delays the response of the drive to any change in the RES
terminal input by the programmed value (see waveforms at F140).
The delay may be increase d to provide additiona l electrical noise imm u n i ty or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number F143
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS

Input Terminal 5 – 12 Response Time

Program Termi nal Input Terminal Delays
This parameter delays the response of the drive to any change in the 5 – 12
terminal inputs by the programmed value (see waveforms at F140).
The delay may be increase d to provide additiona l electrical noise imm u n i ty or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number F144
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS

Input Terminal 13 – 20 Response Time

Program Termi nal Input Terminal Delays
This parameter delays the response of the drive to any change in the 13 – 20
terminal inputs by the programmed value (see waveforms at F140).
The delay may be increase d to provide additiona l electrical noise imm u n i ty or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number F145
Parameter Type — Numerical
Factory Default — 8.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS

Input Terminal 17 (B12) Function

Program Termi nal Input Terminals
This parameter is used to set the fun ct io na l ity of the B12 discrete input
terminal.
In addition, this input terminal m u st be sp e ci fie d as Normally Open or
Normally Closed.
This setting assigns the functionalit y of the programmable B12 terminal to any
one of the user-selectable functions listed in Table 5 on pg. 236.
See the My Function Instruction Manual (P/N 58692) for more information
on the function of this terminal.
Direct Access Number F164
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No

Input Terminal 18 (B13) Function

Program Termi nal Input Terminals
This parameter is used to set the fun ct io na l ity of the B13 discrete input
terminal.
In addition, this input terminal m u st be sp e ci fie d as Normally Open or
Normally Closed.
This setting assigns the function of the programmable B13 terminal to any one
of the user-selectable functions listed in Table 5 on pg. 236.
See the My Function Instruction Manual (P/N 58692) for more information
on the function of this terminal.
Direct Access Number F165
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
F143 F165