F143

F165

Input Terminal 4 (RES) Response Time

Program Terminal Input Terminal Delays

This parameter delays the response of the drive to any change in the RES terminal input by the programmed value (see waveforms at F140).

The delay may be increased to provide additional electrical noise immunity or to prevent the ASD from responding to contact bounce or chatter.

Direct Access Number — F143

Parameter Type — Numerical

Factory Default — 8.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

Input Terminal 5 – 12 Response Time

Program Terminal Input Terminal Delays

This parameter delays the response of the drive to any change in the 5 – 12 terminal inputs by the programmed value (see waveforms at F140).

The delay may be increased to provide additional electrical noise immunity or to prevent the ASD from responding to contact bounce or chatter.

Direct Access Number — F144

Parameter Type — Numerical

Factory Default — 8.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

Input Terminal 13 – 20 Response Time

Program Terminal Input Terminal Delays

This parameter delays the response of the drive to any change in the 13 – 20 terminal inputs by the programmed value (see waveforms at F140).

The delay may be increased to provide additional electrical noise immunity or to prevent the ASD from responding to contact bounce or chatter.

Direct Access Number — F145

Parameter Type — Numerical

Factory Default — 8.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

Input Terminal 17 (B12) Function

Direct Access Number —

F164

Program Terminal Input Terminals

Parameter Type — Selection List

This parameter is used to set the functionality of the B12 discrete input

Factory Default — Unassigned

Changeable During Run — No

terminal.

 

 

In addition, this input terminal must be specified as Normally Open or

 

 

Normally Closed.

 

 

This setting assigns the functionality of the programmable B12 terminal to any

 

 

one of the user-selectable functions listed in Table 5 on pg. 236.

 

 

See the My Function Instruction Manual (P/N 58692) for more information

 

 

on the function of this terminal.

 

 

 

 

 

Input Terminal 18 (B13) Function

Direct Access Number —

F165

Program Terminal Input Terminals

Parameter Type — Selection List

 

Factory Default — Unassigned

This parameter is used to set the functionality of the B13 discrete input

terminal.

Changeable During Run — No

In addition, this input terminal must be specified as Normally Open or Normally Closed.

This setting assigns the function of the programmable B13 terminal to any one of the user-selectable functions listed in Table 5 on pg. 236.

See the My Function Instruction Manual (P/N 58692) for more information on the function of this terminal.