Troubleshooting

Heater Does Not Operate (Direct Spark)

Does not attempt to light (No visible spark)

24 VAC between

terminals W1 and X?

Yes

24 VAC between

terminals 22 and 21?

Yes

24 VAC between

terminals 23 and 21?

Yes

24 VAC between

terminals 24 and 21?

Yes

24 VAC between

terminals 26 and 21?

Yes

Continuity between terminals 26 and 27?

Yes

No

No

No

No

No

No

Heat switch (S4) off.

Turn heat switch (S4) on.

Heat switch not wired.

Wire heat switch (S4).

Main transformer (TR2) defective.

Replace transformer.

(Optional) inlet air sensor (TS4) holding. Adjust TS4 setting.

Reference: Start-Up - Blower, Set-Up Optional Components, pg. 15

Heat relay (RH) defective.

Replace heat relay (RH).

High limit (HLC1) tripped.

Reset, replace high limit (HLC1).

Check on cause of control loss.

(Optional) high/low gas pressure switch(es)

(PS3 and PS4) tripped.

Correct gas pressure and reset.

Reference: Start-Up - Direct Gas, Check the Pilot Gas Pressure, pg. 15

Airflow switch (PS2) holding for proper airflow.

Correct airflow across burner.

Reference: Start-Up - Direct Gas,

Check the Optional High and Low Gas Pressure Switches, pg. 15

At this time the heater should attempt to light.

Model VSU Make-Up Air 29

®

Image 29
Contents Model VSU General Safety Information Installation, Operation and Maintenance ManualReceiving Inspection and Maintenance during StorageUnpacking HandlingTable of Contents Subassemblies Product OverviewOpen View Burner, Blower and Control Center SectionDampers Burner SubassemblyControl Center Installation Service Platform Material List Complete InstallationInstallation of Optional Service Platform Figure C AssemblyInstallation of Electrical Wiring Determine the Supply Gas Requirements Installation of Direct Gas PipingInstall Additional Regulator if Required Installation of Building Pressure Control optional Check blower rotation Check for vibration Supply fan RPM Start-Up ChecklistUnit Model Number Start-Up Blower Start-Up Direct Gas Check the Optional High and Low Gas Pressure SwitchesSet-Up Optional Components Check the Supply Gas PressureSet the Burner Air Pressure Differential Maximum firing rate adjustmentSet the Maximum Firing Rate Measuring the Pressure DropSet the Minimum Firing Rate Regulators and Modulating ValvesMaxitrol Series 44 9 Terminals The Maxitrol Set the Unit’s Operating TemperatureFlame Signal Check Pilot Ignition Operation VAV Units optional Variable Volume OperationSpeed ModulatingOperation Electrical Operation Recirculating Units optionalRecirculation Operation Electrical Sequence Exhaust Fan Contact S1 Closed optional3a. Heat Contact S4 Closed Pilot Ignition Flame Safeguard FSG Sequence3b. Heat Contact S4 Closed Direct Spark Heat Contact ClosedBlower Does Not Operate TroubleshootingMotor Overamps Too Much Airflow Insufficient AirflowExcessive Noise or Vibration Does not attempt to light No visible spark Heater Does Not Operate Pilot IgnitionAttempts to light, but no pilot visible spark Between 0.625 and 0.675 in. WC? Visible pilotHeater Does Not Operate Direct Spark Attempts to light, but no flame Visible spark Belt Drives Maintenance RoutineMotors WheelsMaintenance Fall Reference Typical Gas Train Layout with Direct Spark Ignition Fan Relay allows power to pass to energize motor starter Dirty Filter SwitchHeat Relay allows power to pass to heating controls Control Center LayoutDateTime AM/PM Maintenance LogWarranty

470654 specifications

Greenheck Fan 470654 is a cutting-edge ventilation solution designed to meet the demanding requirements of commercial and industrial applications. Renowned for its reliability and efficiency, this fan model integrates advanced technologies and engineering to provide optimal air movement and control.

One of the standout features of the Greenheck Fan 470654 is its robust construction. Designed with high-quality materials, the fan promotes longevity and durability, making it suitable for use in tough environments. This fan features a heavy-gauge steel housing that minimizes vibration and enhances noise reduction, contributing to a quieter operation, a critical factor in maintaining a serene working environment.

The fan is equipped with a powerful motor that ensures efficient airflow, achieving high performance while consuming minimal energy. This energy efficiency is emphasized through the use of advanced motor technology, including variable frequency drive (VFD) compatibility. VFDs allow for precise control of the fan speed, enabling adjustments based on system demand, thus significantly reducing energy consumption and operating costs.

In terms of airflow performance, the Greenheck Fan 470654 is engineered to provide a high volume of air movement while maintaining static pressure. Its aerodynamic design minimizes resistance, enhancing overall efficiency. The fan is designed to operate across a range of static pressures, making it versatile for different applications, from commercial kitchens to large manufacturing facilities.

Additionally, the fan's installation is straightforward, thanks to its user-centric design. The model incorporates mounting brackets and options for various duct configurations, ensuring seamless integration into existing systems. Maintenance is also made easier with accessible components, allowing technicians to perform regular checks and upkeep without extensive downtime.

Safety features are a priority in the design of the Greenheck Fan 470654. It includes protective features such as thermal overload protection to prevent motor damage and extend operational life. The fan's design also adheres to industry standards and regulations, providing peace of mind for users.

In summary, the Greenheck Fan 470654 is a well-engineered solution that combines durability, efficiency, and advanced technology to deliver superior performance in ventilation applications. With its powerful motor, energy-saving capabilities, and ease of installation and maintenance, it stands out as a reliable choice for professionals seeking optimal airflow management.