Introduction

LX-Bus™ Operation

6.1Description

The XR2500F Command Processor™ panel supports LX-Bus operation directly from the panel. Each LX-Bus circuit provides 100 additional zones. Use J22 LX-Bus Header for the first 100 zones. Use the installed 481 Zone Expansion Interface Card for the next 100 zones. This provides a total of 200 expansion zones. To install up to four additional Interface Cards use a Model 461 Interface Adaptor Card.

6.2XR2500F On-board LX-Bus

To enable J22 to operate as an LX-Bus, place a jumper on the two pins next to the letter “L” on the J23 6Pin header. When using J22 as an LX-Bus, connect a DMP Model 300 4-wire Harness to the J22 4-pin header labeled LX-BUS. This provides the first 100 LX-Bus zones numbered 500-599. Respect wire colors when connecting devices and use all four wires. Reset the panel using the J16 jumper to activate LX-Bus operation. See Connecting LX-Bus and Keypad Devices section for maximum wiring distances.

Note: Do NOT use shielded wire when using the LX-Bus. Do NOT connect the wires from the 4-wire harness to the panel terminals.

6.3LX-Bus 481 Zone Expansion Interface Card

The 481 Zone Expansion Interface Card provides an additional 100 zones to the XR2500F. When used in conjunction with the on-board J22 LX-Bus the 481 LX-Bus zones are numbered 600 to 699.

6.4Installing the 481 Card

Remove AC and battery power from the XR2500F panel and ground yourself before handling and installing the 481 Card.

1.Align the 481 Card 50 pin connector with the XR2500F panel J6 connector.

2.Press the 481 onto the J6 connector while applying even pressure to both sides.

 

Command Processor

 

 

 

 

 

Panel

 

 

 

 

 

 

 

 

J6 Interface Card

 

481 Zone

 

 

 

 

 

Expansion

 

 

 

 

Connector

 

 

 

 

 

 

 

 

 

 

Interface

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Card

 

 

 

Zone Expansion

 

 

 

 

 

 

Harness Connectors

 

 

Z5

GND

Z6

Z7

GND

Z8

Z9+ Z9- Z10+ Z10-

18

19

20

21

22

23

24

25

26

27

28

To LX-Bus Modules

Red—Auxiliary Power

Yellow—Data In

Green—Data Out

Black—Ground

Figure 6: 481 Wiring

Digital Monitoring Products

XR2500F Installation Guide

8

Image 16 Contents
Installation Guide Model XR2500F Command Processor Installation Guide Secondary Power Supply Fire Command CenterIntroduction MountingAccessory Devices Battery InformationPowered Zones for 2-Wire Smoke Detectors J22 LX-Bus Expansion ConnectorJ1 Ethernet Connector Reset and Tamper HeadersListed Compliance Specifications Universal UL Burglary SpecificationsHoldup Alarm Units Digital Burglar Alarm Communicator System Units ANSI/ ULPolice Station Connected and Local Burglar Alarm Units Access Control System UnitsCalifornia State Fire Marshal Specifications New York City MEA SpecificationsWiring Diagrams Household Fire Warning System Units ANSI/UL 985, NfpaThis page intentionally left blank Introduction LX-Bus OutputsRelays Zone ReferenceMounting Wiring Diagram Use MarkingTransformers and AC Power Connection AC Connection16 VAC Transformer Earth Ground GNDBattery Connection to XR2500F Command Processor panel Secondary Power SupplyDescription Connection Two 866 NAC ModulesBell Silence/Bell Trouble Installing the 481 Card LX-Bus OperationXR2500F On-board LX-Bus LX-Bus 481 Zone Expansion Interface Card893A Dual Phone Line Module Notification FCC RegistrationFire Command Center Remote Fire Command CenterZone Expansion ExpansionOutput Expansion Accessory Devices Lightning ProtectionAccessory Devices Connecting LX-Bus and Keypad Bus Devices Mounting Keypads and Zone Expansion ModulesBattery Information 11.7 XR2500F Standby Battery Calculations Copy Sub-Totals to nextThis page only Standby Battery Selection Bell Output Keypad BusPowered Zones for 2-Wire Smoke Detectors Smoke and Glassbreak Detector OutputTerminals 11 Current RatingCompatible 2-Wire Smoke Detector Chart DS250HDKeyswitch Arming Zone Protection ZonesTerminals Operational ParametersDry Contact Relay Outputs Output Harness WiringContact Rating Model 300 Harness Wiring J11 Annunciator OutputsJ23 6-Pin Header Model 860 Relay ModuleJ22 LX-Bus Expansion Connector J21 Serial ConnectorSerial Connector LEDs LX-Bus Interface CardsJ1 Ethernet Connector Reset and Tamper Headers23.1 J16 Reset Header Ethernet LEDsListed Compliance Specifications Universal UL Burglary SpecificationsHousehold Burglar-Alarm System Units ANSI/UL Area InformationProprietary Dialer Dact Central StationStandard or Encrypted Line Security Model 463G Cell Only, Standard or Encrypted Line SecurityPath 1 programming Path 2 programming Path 3 programming Digital Burglar Alarm Communicator System Units ANSI/ UL Holdup Alarm UnitsPolice Station Connected and Local Burglar Alarm Units Bell Automatic Bell TestPath 1 programming Path 2 programming Path 3 programming Access Control System Units MercantilePanel Designation Compatible DevicesUniversal Fire Alarm Specifications Power Supply Power Fail DelayLocal Protective Signaling Systems Remote Station Protective Signaling SystemsGround Fault Household Fire Warning System Units ANSI/UL 985, NfpaNotification Appliances Cross ZoningCalifornia State Fire Marshal Specifications New York City MEA SpecificationsDigital Dialer and Network Communication Communication ProgrammingWiring Diagrams Prewired 866 Modules with NAC ExtenderWiring Diagrams Alarm Bell PWR Bell Out + Bell Trouble DSM-12/24 Module 39.5 867 Class B Style W Notification Appliance Circuit To initiating zoneTo initiating zone DMP Model Dual Style D Zone Module Installation Command Processor Panel Remote Station Reversing Relay ConnectionSecond LX-Bus with Auxiliary Power Supply XR2500F 481 Command Processor PanelLX-Bus Module Connection Powered Burglary Devices Model 860 Relay Module ConnectionRevisions to This Document Ver Section Number and Heading Quick Explanation of ChangesThis page intentionally left blank Operating Instructions Model XR2500F Panels Mounting Instructions Listings and Approvals