DMP Electronics XR2500F manual Mounting

Page 11
Holes for Surface Mounting
Holes for 1" screws for
Flush Mounting
Battery Shelf
Additional Holes for Surface Mounting
Hole for Flush Mounting
Figure 1: Mounting the XR2500F Enclosure

Introduction

Mounting

2.1Mounting the Enclosure

The XR2500F must be mounted in a secure,

 

 

 

 

3/4" X 1/2" Knockouts

dry location to protect the unit from damage

 

 

 

 

due to tampering and the elements. The

 

 

 

 

Hole for Flush

enclosure can be either flush mounted or

 

 

Mounting

surface mounted and includes a hinged door

 

 

 

with lock. The hole in the enclosure door

 

 

 

allows access to the Fire Command Center

 

 

 

without opening the door. Figure 1 illustrates

 

 

 

the mounting hole locations for the panel

 

 

 

enclosure.

 

 

 

The enclosure dimensions are 32” tall, 14.5” wide, by 4” deep. The lid adds about 0.5” to each side.

2.2Surface Mounting

The enclosure center hole should be attached to a wall stud. Due to the enclosure weight, especially the batteries, it is extremely important to mount the enclosure on the stud. Attach the two holes beside the center hole to sheetrock to secure enclosure. When mounting the enclosure, be sure to leave room for the panel door to swing open. The door lock should be easily accessible.

2.3Flush Mounting

The enclosure can also be flush mounted. Use 1” screws to secure the enclosure between two studs using the two sets of holes on

the sides of the enclosure. Use the top and bottom holes to secure to horizontal studs, if necessary.

2.4 Fire Command Center LCD

Keyboard

A Fire Command Center LCD Keyboard has been factory installed on the XR2500F enclosure. A keyswitch has also been installed and pre-wired to the left of the keyboard. The user can turn the keyswitch to enable the four function keys without opening the enclosure door.

2.5 Metal Backplate

The XR2500F components are pre-wired and installed on a metal backplate. The

backplate can be easily removed to keep components safe during pre-wire activities.

Remove AC and battery power from the XR2500F panel before removing the backplate. Disconnect all battery, transformer, and the Fire Command Center LCD keyboard wires. From the panel, disconnect the AC wires from terminals 1 and 2. Disconnect the battery wires either from the batteries or the panel terminals 3 and 4. Finally, disconnect the keyboard wires from panel terminals 7, 8, 9, and 10.

Remove the screws securing the backplate to the enclosure. Loosen the two top screws that the backplate hangs on. After loosening and removing the screws, lift the backplate up slightly and pull the backplate toward you. When reinstalling the backplate, be sure all connections are secure.

Figure 2 illustrates the backplate and the components. The backplate is shown in light gray.

XR2500F Installation Guide

Digital Monitoring Products

3

Image 11
Contents Installation Guide Model XR2500F Command Processor Installation Guide Mounting Secondary Power SupplyFire Command Center IntroductionJ22 LX-Bus Expansion Connector Accessory DevicesBattery Information Powered Zones for 2-Wire Smoke DetectorsUniversal UL Burglary Specifications J1 Ethernet ConnectorReset and Tamper Headers Listed Compliance SpecificationsAccess Control System Units Holdup Alarm UnitsDigital Burglar Alarm Communicator System Units ANSI/ UL Police Station Connected and Local Burglar Alarm UnitsHousehold Fire Warning System Units ANSI/UL 985, Nfpa California State Fire Marshal SpecificationsNew York City MEA Specifications Wiring DiagramsThis page intentionally left blank Introduction Zone Reference LX-BusOutputs RelaysMounting Use Marking Wiring DiagramEarth Ground GND Transformers and AC Power ConnectionAC Connection 16 VAC TransformerDescription Secondary Power SupplyBattery Connection to XR2500F Command Processor panel Bell Silence/Bell Trouble Two 866 NAC ModulesConnection LX-Bus 481 Zone Expansion Interface Card Installing the 481 CardLX-Bus Operation XR2500F On-board LX-Bus893A Dual Phone Line Module FCC Registration NotificationRemote Fire Command Center Fire Command CenterOutput Expansion ExpansionZone Expansion Lightning Protection Accessory DevicesAccessory Devices Mounting Keypads and Zone Expansion Modules Connecting LX-Bus and Keypad Bus DevicesBattery Information Copy Sub-Totals to next 11.7 XR2500F Standby Battery CalculationsThis page only Standby Battery Selection Keypad Bus Bell OutputCurrent Rating Powered Zones for 2-Wire Smoke DetectorsSmoke and Glassbreak Detector Output Terminals 11DS250HD Compatible 2-Wire Smoke Detector ChartOperational Parameters Keyswitch Arming ZoneProtection Zones TerminalsContact Rating Output Harness WiringDry Contact Relay Outputs Model 860 Relay Module Model 300 Harness WiringJ11 Annunciator Outputs J23 6-Pin HeaderLX-Bus Interface Cards J22 LX-Bus Expansion ConnectorJ21 Serial Connector Serial Connector LEDsEthernet LEDs J1 Ethernet ConnectorReset and Tamper Headers 23.1 J16 Reset HeaderUniversal UL Burglary Specifications Listed Compliance SpecificationsArea Information Household Burglar-Alarm System Units ANSI/ULModel 463G Cell Only, Standard or Encrypted Line Security Proprietary DialerDact Central Station Standard or Encrypted Line SecurityPath 1 programming Path 2 programming Path 3 programming Police Station Connected and Local Burglar Alarm Units Holdup Alarm UnitsDigital Burglar Alarm Communicator System Units ANSI/ UL Automatic Bell Test BellPath 1 programming Path 2 programming Path 3 programming Compatible Devices Access Control System UnitsMercantile Panel DesignationUniversal Fire Alarm Specifications Remote Station Protective Signaling Systems Power SupplyPower Fail Delay Local Protective Signaling SystemsCross Zoning Ground FaultHousehold Fire Warning System Units ANSI/UL 985, Nfpa Notification AppliancesCommunication Programming California State Fire Marshal SpecificationsNew York City MEA Specifications Digital Dialer and Network CommunicationPrewired 866 Modules with NAC Extender Wiring DiagramsWiring Diagrams Alarm Bell PWR Bell Out + Bell Trouble DSM-12/24 Module To initiating zone 39.5 867 Class B Style W Notification Appliance CircuitTo initiating zone DMP Model Dual Style D Zone Module Installation Remote Station Reversing Relay Connection Command Processor PanelXR2500F 481 Command Processor Panel Second LX-Bus with Auxiliary Power SupplyLX-Bus Module Connection Model 860 Relay Module Connection Powered Burglary DevicesVer Section Number and Heading Quick Explanation of Changes Revisions to This DocumentThis page intentionally left blank Mounting Instructions Listings and Approvals Operating Instructions Model XR2500F Panels

XR2500F specifications

The DMP Electronics XR2500F is an advanced and versatile electronic device designed to cater to a wide range of applications including industrial automation, robotics, and smart home technologies. Known for its robust performance and reliable functionalities, the XR2500F stands out as a leading option in the market.

One of the main features of the XR2500F is its powerful processing unit, which ensures efficient handling of complex tasks and data processing. With a clock speed of up to 2.5 GHz, the device is capable of multitasking, enabling users to run multiple applications simultaneously without compromising performance. This makes the XR2500F an ideal choice for applications that require real-time data processing and analysis.

The XR2500F is equipped with an extensive array of connectivity options, including Wi-Fi, Bluetooth, and Ethernet capabilities. This allows for seamless integration with various devices and networks. The wireless options facilitate easy communication with cloud services and other IoT devices, making it suitable for smart home automation systems, where synchronization and control are critical.

In terms of memory, the XR2500F offers significant storage capacity, with options that can accommodate up to 64GB of RAM and 512GB of flash storage. This ample memory ensures that users can store large amounts of data and run memory-intensive applications without experiencing slowdowns. Additionally, the device supports expandable memory options, allowing for future upgrades to meet growing demands.

The XR2500F also incorporates advanced security technologies to protect sensitive data. Features like end-to-end encryption and secure boot processes safeguard against unauthorized access and data breaches. This is particularly important in industrial settings where data integrity is critical for operational safety.

Another remarkable characteristic of the XR2500F is its energy efficiency. Designed with the latest power management technologies, the device minimizes energy consumption while maximizing performance. This not only reduces operational costs but also aligns with green technology initiatives.

Overall, the DMP Electronics XR2500F is a high-performance electronic device that combines powerful processing, extensive connectivity, robust memory, enhanced security, and energy efficiency. Its versatility and reliability make it a preferred choice for professionals seeking innovative solutions in automation and control systems.