DMP Electronics XR2500F manual Automatic Bell Test

Page 41

Compliance

31.4 Bell

A local audible signal appliance must be used such as Ademco AB12M bell and bell housing.

The alarm housing for a mercantile alarm system without a remote alarm transmission connection shall be mounted on the outside of the building, visible from a public street or highway. It shall be accessible for examination and repair. It shall also be located not more than four stories above the street level unless:

a)A second alarm sounding device and housing, intended for outside service, is mounted adjacent to the premises or area of the building in which the alarm system is installed or

b)A second alarm sounding device, intended for inside service, is mounted within the premises.

In either case, the outside alarm sounding device and housing may be mounted as high as the seventh floor.

31.5 Bell Cutoff

The Bell Cutoff time cannot be less than 15 minutes.

31.6 Automatic Bell Test

The Automatic Bell Test option must be programmed as YES.

31.7 Standard or Encrypted Line Security

Standard Line Security is provided when configured as a Path 1 NET system using an XR500N panel or an XR500 panel with an iCOM™ Network Alarm Router. The NET Check-in time must be set to 06 minutes or RDM. When programmed for Standard Line Security, Exit Time Restart is disabled. When a dialer is required for 06 minute check-in time, an attack resistant enclosure (DMP Model 350A) is required. When the check-in time is set to a number less than 200 seconds, an attack resistant enclosure is not required.

To provide Encrypted Line security, install an XR500E panel or an XR500 panel with an iCOM-E™ Encrypted Network Alarm Router.

For Encrypted Line security operation, communication between the Premise and Supervising Station provides 128 bit encryption when using an XR500E panel or an XR500 panel with an iCOM-E Encrypted Network Alarm Router.

31.8 Wireless Audible Annunciation Option

The Wireless Audible option must be selected as ANY for commercial applications.

31.9 Model 463G CELL Only, Standard or Encrypted Line Security

Standard or Encrypted Line Security is provided when programmed using CELL with no backup. XR500 cellular communication is used as primary with a 3 minute check-in when armed or disarmed.

Path 1 programming

 

Comm Type: = CELL

Checkin: = 3 minute

 

 

Path Type: = Primary

Fail Time: = 3 minute

Encrypt: = NO or YES*

Test Rpt: = NO

 

 

Sub Code: = NO or YES

 

*For Encrypted Line Security, program a Passphrase in Network Options.

XR2500F Installation Guide

Digital Monitoring Products

33

Image 41
Contents Installation Guide Model XR2500F Command Processor Installation Guide Fire Command Center Secondary Power SupplyIntroduction MountingBattery Information Accessory DevicesPowered Zones for 2-Wire Smoke Detectors J22 LX-Bus Expansion ConnectorReset and Tamper Headers J1 Ethernet ConnectorListed Compliance Specifications Universal UL Burglary SpecificationsDigital Burglar Alarm Communicator System Units ANSI/ UL Holdup Alarm UnitsPolice Station Connected and Local Burglar Alarm Units Access Control System UnitsNew York City MEA Specifications California State Fire Marshal SpecificationsWiring Diagrams Household Fire Warning System Units ANSI/UL 985, NfpaThis page intentionally left blank Introduction Outputs LX-BusRelays Zone ReferenceMounting Use Marking Wiring DiagramAC Connection Transformers and AC Power Connection16 VAC Transformer Earth Ground GNDDescription Secondary Power SupplyBattery Connection to XR2500F Command Processor panel Bell Silence/Bell Trouble Two 866 NAC ModulesConnection LX-Bus Operation Installing the 481 CardXR2500F On-board LX-Bus LX-Bus 481 Zone Expansion Interface Card893A Dual Phone Line Module FCC Registration NotificationRemote Fire Command Center Fire Command CenterOutput Expansion ExpansionZone Expansion Lightning Protection Accessory DevicesAccessory Devices Mounting Keypads and Zone Expansion Modules Connecting LX-Bus and Keypad Bus DevicesBattery Information Copy Sub-Totals to next 11.7 XR2500F Standby Battery CalculationsThis page only Standby Battery Selection Keypad Bus Bell OutputSmoke and Glassbreak Detector Output Powered Zones for 2-Wire Smoke DetectorsTerminals 11 Current RatingDS250HD Compatible 2-Wire Smoke Detector ChartProtection Zones Keyswitch Arming ZoneTerminals Operational ParametersContact Rating Output Harness WiringDry Contact Relay Outputs J11 Annunciator Outputs Model 300 Harness WiringJ23 6-Pin Header Model 860 Relay ModuleJ21 Serial Connector J22 LX-Bus Expansion ConnectorSerial Connector LEDs LX-Bus Interface CardsReset and Tamper Headers J1 Ethernet Connector23.1 J16 Reset Header Ethernet LEDsUniversal UL Burglary Specifications Listed Compliance SpecificationsArea Information Household Burglar-Alarm System Units ANSI/ULDact Central Station Proprietary DialerStandard or Encrypted Line Security Model 463G Cell Only, Standard or Encrypted Line SecurityPath 1 programming Path 2 programming Path 3 programming Police Station Connected and Local Burglar Alarm Units Holdup Alarm UnitsDigital Burglar Alarm Communicator System Units ANSI/ UL Automatic Bell Test BellPath 1 programming Path 2 programming Path 3 programming Mercantile Access Control System UnitsPanel Designation Compatible DevicesUniversal Fire Alarm Specifications Power Fail Delay Power SupplyLocal Protective Signaling Systems Remote Station Protective Signaling SystemsHousehold Fire Warning System Units ANSI/UL 985, Nfpa Ground FaultNotification Appliances Cross ZoningNew York City MEA Specifications California State Fire Marshal SpecificationsDigital Dialer and Network Communication Communication ProgrammingPrewired 866 Modules with NAC Extender Wiring DiagramsWiring Diagrams Alarm Bell PWR Bell Out + Bell Trouble DSM-12/24 Module To initiating zone 39.5 867 Class B Style W Notification Appliance CircuitTo initiating zone DMP Model Dual Style D Zone Module Installation Remote Station Reversing Relay Connection Command Processor PanelXR2500F 481 Command Processor Panel Second LX-Bus with Auxiliary Power SupplyLX-Bus Module Connection Model 860 Relay Module Connection Powered Burglary DevicesVer Section Number and Heading Quick Explanation of Changes Revisions to This DocumentThis page intentionally left blank Mounting Instructions Listings and Approvals Operating Instructions Model XR2500F Panels

XR2500F specifications

The DMP Electronics XR2500F is an advanced and versatile electronic device designed to cater to a wide range of applications including industrial automation, robotics, and smart home technologies. Known for its robust performance and reliable functionalities, the XR2500F stands out as a leading option in the market.

One of the main features of the XR2500F is its powerful processing unit, which ensures efficient handling of complex tasks and data processing. With a clock speed of up to 2.5 GHz, the device is capable of multitasking, enabling users to run multiple applications simultaneously without compromising performance. This makes the XR2500F an ideal choice for applications that require real-time data processing and analysis.

The XR2500F is equipped with an extensive array of connectivity options, including Wi-Fi, Bluetooth, and Ethernet capabilities. This allows for seamless integration with various devices and networks. The wireless options facilitate easy communication with cloud services and other IoT devices, making it suitable for smart home automation systems, where synchronization and control are critical.

In terms of memory, the XR2500F offers significant storage capacity, with options that can accommodate up to 64GB of RAM and 512GB of flash storage. This ample memory ensures that users can store large amounts of data and run memory-intensive applications without experiencing slowdowns. Additionally, the device supports expandable memory options, allowing for future upgrades to meet growing demands.

The XR2500F also incorporates advanced security technologies to protect sensitive data. Features like end-to-end encryption and secure boot processes safeguard against unauthorized access and data breaches. This is particularly important in industrial settings where data integrity is critical for operational safety.

Another remarkable characteristic of the XR2500F is its energy efficiency. Designed with the latest power management technologies, the device minimizes energy consumption while maximizing performance. This not only reduces operational costs but also aligns with green technology initiatives.

Overall, the DMP Electronics XR2500F is a high-performance electronic device that combines powerful processing, extensive connectivity, robust memory, enhanced security, and energy efficiency. Its versatility and reliability make it a preferred choice for professionals seeking innovative solutions in automation and control systems.