Page 39

Installation

28.11 Model 463G NET with CELL as Alternate Primary and Dialer Backup, Standard or Encrypted Line Security

Standard or Encrypted Line Security is provided using NET communication with CELL as an alternate primary and with digital dialer as a backup. XR500 network communication is used as primary with a 6 minute check-in when armed, and a random check-in over a 60 minute period when disarmed. CELL is the backup path and set to daily test. Should the NET primary path become disabled, CELL adapts the same check-in time programmed for the primary communication and becomes an alternate primary path. The dialer path is used as the backup if both NET and CELL fail to receive acknowledgement from the receiver.

This method of operation causes the CELL alternate primary to adapt to the 6 minute NET primary check-in rate when the NET primary is unavailable maintaining line supervision and precludes the need for a central station runner to respond to the NET primary failure.

Path 1 programming

Path 2 programming

Path 3 programming

Comm Type: = NET

Comm Type: = CELL

Comm Type: = DD

Path Type: = Primary

Path Type: = Backup

Path Type: = Backup

 

(operates as alternate

(operates as second

 

primary)

method)

Test Rpt: = NO

Test Rpt: = YES

Test Rpt: = YES

Checkin: = 6 minute, or RND

Test Freq: = Daily

Test Freq: = Daily

(random)

 

 

Fail Time: = 6 minute, or RND

Checkin: = ADAPT

Duplicate Alarms: = YES

(random)

 

 

Encrypt: = NO or YES*

Encrypt: = NO or YES*

 

Sub Code: = YES

Sub Code: = Shared

 

*For Encrypted Line Security, program a Passphrase in Network Options.

28.12 Model 463G NET with CELL as Backup and Adaptive Primary, Standard or Encrypted Line Security

Standard or Encrypted Line Security is provided when programmed using NET communication and CELL as backup and as needed adapts and takes over as primary. XR500 network communication is used as primary with a 6 minute check-in when armed, and a random check-in over a 60 minute period when disarmed. CELL is the backup path and set to daily test. Should the primary path become disabled, the CELL adapts to a special 3 minute check-in time and because of that check-in rate becomes the primary without the requirement of a backup. This method of operation causes the CELL backup to adapt to the 3 minute check- in rate when the NET primary is unavailable becoming a standalone primary without the need for a backup. This maintains line supervision and precludes the need for a central station runner to respond to the NET primary failure.

Path 1 programming

Path 2 programming

Comm Type: = NET

Comm Type: = CELL

Path Type: = Primary

Path Type: = Backup (operates as second

 

method)

Test Rpt: = NO

Test Rpt: = YES

Checkin: = 6 minute, or RND

Test Freq: = Daily

(random)

 

Fail Time: = 6 minute, or RND

Checkin: = ADAPT3

(random)

 

Encrypt: = NO or YES*

Encrypt: = NO or YES*

Sub Code: = YES

Duplicate Alarms: = YES

 

Sub Code: = Shared

*For Encrypted Line Security, program a Passphrase in Network Options.

XR2500F Installation Guide

Digital Monitoring Products

31

Image 39 Contents
Installation Guide Model XR2500F Command Processor Installation Guide Mounting Secondary Power SupplyFire Command Center IntroductionJ22 LX-Bus Expansion Connector Accessory DevicesBattery Information Powered Zones for 2-Wire Smoke DetectorsUniversal UL Burglary Specifications J1 Ethernet ConnectorReset and Tamper Headers Listed Compliance SpecificationsAccess Control System Units Holdup Alarm UnitsDigital Burglar Alarm Communicator System Units ANSI/ UL Police Station Connected and Local Burglar Alarm UnitsHousehold Fire Warning System Units ANSI/UL 985, Nfpa California State Fire Marshal SpecificationsNew York City MEA Specifications Wiring DiagramsThis page intentionally left blank Introduction Zone Reference LX-BusOutputs RelaysMounting Use Marking Wiring DiagramEarth Ground GND Transformers and AC Power ConnectionAC Connection 16 VAC TransformerSecondary Power Supply Battery Connection to XR2500F Command Processor panelDescription Two 866 NAC Modules ConnectionBell Silence/Bell Trouble LX-Bus 481 Zone Expansion Interface Card Installing the 481 CardLX-Bus Operation XR2500F On-board LX-Bus893A Dual Phone Line Module FCC Registration NotificationRemote Fire Command Center Fire Command CenterExpansion Zone ExpansionOutput Expansion Lightning Protection Accessory DevicesAccessory Devices Mounting Keypads and Zone Expansion Modules Connecting LX-Bus and Keypad Bus DevicesBattery Information Copy Sub-Totals to next 11.7 XR2500F Standby Battery CalculationsThis page only Standby Battery Selection Keypad Bus Bell OutputCurrent Rating Powered Zones for 2-Wire Smoke DetectorsSmoke and Glassbreak Detector Output Terminals 11DS250HD Compatible 2-Wire Smoke Detector ChartOperational Parameters Keyswitch Arming ZoneProtection Zones TerminalsOutput Harness Wiring Dry Contact Relay OutputsContact Rating Model 860 Relay Module Model 300 Harness WiringJ11 Annunciator Outputs J23 6-Pin HeaderLX-Bus Interface Cards J22 LX-Bus Expansion ConnectorJ21 Serial Connector Serial Connector LEDs Ethernet LEDs J1 Ethernet Connector Reset and Tamper Headers 23.1 J16 Reset HeaderUniversal UL Burglary Specifications Listed Compliance SpecificationsArea Information Household Burglar-Alarm System Units ANSI/ULModel 463G Cell Only, Standard or Encrypted Line Security Proprietary DialerDact Central Station Standard or Encrypted Line SecurityPath 1 programming Path 2 programming Path 3 programming Holdup Alarm Units Digital Burglar Alarm Communicator System Units ANSI/ ULPolice Station Connected and Local Burglar Alarm Units Automatic Bell Test BellPath 1 programming Path 2 programming Path 3 programming Compatible Devices Access Control System UnitsMercantile Panel DesignationUniversal Fire Alarm Specifications Remote Station Protective Signaling Systems Power SupplyPower Fail Delay Local Protective Signaling SystemsCross Zoning Ground FaultHousehold Fire Warning System Units ANSI/UL 985, Nfpa Notification AppliancesCommunication Programming California State Fire Marshal SpecificationsNew York City MEA Specifications Digital Dialer and Network CommunicationPrewired 866 Modules with NAC Extender Wiring DiagramsWiring Diagrams Alarm Bell PWR Bell Out + Bell Trouble DSM-12/24 Module To initiating zone 39.5 867 Class B Style W Notification Appliance CircuitTo initiating zone DMP Model Dual Style D Zone Module Installation Remote Station Reversing Relay Connection Command Processor PanelXR2500F 481 Command Processor Panel Second LX-Bus with Auxiliary Power SupplyLX-Bus Module Connection Model 860 Relay Module Connection Powered Burglary DevicesVer Section Number and Heading Quick Explanation of Changes Revisions to This DocumentThis page intentionally left blank Mounting Instructions Listings and Approvals Operating Instructions Model XR2500F Panels