Bosch Appliances F220-B6 installation manual Install the Bases, Mount the Bases

Page 10

10 en Install the Bases

F220 Series Detectors with F220-B6/C/E/R Bases

 

 

providing tamper protection. An EOL power supervision module, such as a D275 or an F220-B6E Power Supervision Base and an EOL resistor as specified by the control panel manufacturer, supervises power.

3 Install the Bases

3.1Mount the Bases

With the exception of the F220-B6E base, all four-wire bases can be used in any combination within a loop. One F220-B6E Power Supervision Base can be used as the last base on a loop in four-wire systems to provide power supervision.

NOTE! Follow NFPA 72 guidelines for mounting locations.

i For commercial and industrial installations, 30 ft (9 m) spacing between smoke detectors is recommended.

1.Release the mounting skirt from the mounting base. Use a screwdriver at the location of the snap locks (refer to Figure 2.1, item 12, page 5) to release the mounting skirt.

2.Run all system wiring (refer to Section 3.2 Wire the Bases).

3.Mount the base using the two oblong mounting holes. Fits 4 in. square, octagon, AB, and single-gang back boxes.

NOTE! Depending on local regulations, you can surface

i mount the bases using anchors, mollies, or wing nuts, or you can mount directly on back boxes.

NOTE! The electrical box must be large enough to

i accommodate the number and size of conductors specified by the National Electrical Code or any local authorities having jurisdiction (AHJ).

4.Tighten the base to the mounting surface. Tighten until snug, but not distorted.

4998138694 -04 2007.01

Installation Manual

Bosch Security Systems, Inc.

Image 10
Contents F220 Series Detectors with F220-B6/C/E/R Bases Legal Required Maintenance and TestingTrademarks F220-B6 Series Detector Bases General InformationCompatible Control Panels Base Comparisons Base Features F220 Series Detectors About F220 Series Detector Heads2 F220 Series Detector Features 3 F220 Series Heat Detector HeadsGeneral Specifications Technical Specifications4 F220 Series Smoke Detector Heads Detector Specifications Base SpecificationsElectrical Supervision Install the Bases Mount the BasesTerminal Connections Wire the BasesLoop Wiring Specifications EOL ResistorsWire Optional Remote Annunciators Four-wire Loop TerminationWire F220-B6 Two-wire Bases Wire F220-B6C/E/R Four-wire Bases1 F220-B6C 2 F220-B6EF220-B6E 3 F220-B6R F220-B6RWire F220-B6E Power Supervision Base Wire Power Supervision ModulesWire D275 Power Supervision Module Mount the Detector Heads Install the Detector HeadsOptional Locking Bar Mounting Skirt LEDDetector Head Keyed. Do not force them onto the mounting basesSensitivity Mode Test ModeSet Detector Modes Set CleanMe Feature Flash Rate and Trouble IndicationTest the Installation Inspect the InstallationReset the Control Panel Activate an Alarm at Each DetectorTest Each Detector Perform Nfpa 72 Required Testing Test the Alarm LoopTest CO Sensors Page Page USA