Bosch Appliances installation manual F220-B6E

Page 15

F220 Series Detectors with F220-B6/C/E/R Bases

Install the Bases en 15

 

 

unnecessary. Use only one F220-B6E per zone run. It must be the last base on the run. Refer to Figure 3.4 for wiring details.

 

_

 

 

 

 

 

1

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

b2

b1

 

 

a1/a2

c

F220-B6E*

C

NO

 

3 C

 

 

 

5

4

 

 

 

 

5

 

 

2NO

 

 

 

 

 

1

6

 

 

 

 

 

 

 

 

 

 

 

 

 

+

3

 

 

 

 

2

 

 

 

 

 

_

 

 

 

 

 

1. Power input (positive [+]

 

previous four-wire base.

in on terminal b2; negative

3.

Jumper connecting

[-] in on terminal a1/a2)

 

terminals 2 and 3.

from the control panel or

4.

Place an appropriate EOL

from a previous four-wire

 

resistor (refer to the

base.

 

control panel’s installation

2. Initiating device circuit

 

instructions for resistor

(IDC) input (positive [+] to

 

specifications) across

terminal 2 and negative [-]

 

Terminals 1 and 4.

to terminal 1) from the

5.

Power Supervision Relay

control panel or from a

6.

Alarm Loop Relay

 

 

 

Fig. 3.4 Wiring F220-B6E Four-wire Power Supervision Bases

* F220-B6E Bases can only be used at the end of a loop.

The alarm loop relay (Form A, Terminals 1 and 2) and the power supervision relay (Terminal 3 and 4) are rated for 0.5 A at 120 VAC/DC for resistive loads.

Bosch Security Systems, Inc.

Installation Manual

4998138694 -04 2007.01

Image 15
Contents F220 Series Detectors with F220-B6/C/E/R Bases Required Maintenance and Testing LegalTrademarks General Information F220-B6 Series Detector BasesCompatible Control Panels Base Comparisons Base Features About F220 Series Detector Heads F220 Series Detectors3 F220 Series Heat Detector Heads 2 F220 Series Detector FeaturesTechnical Specifications General Specifications4 F220 Series Smoke Detector Heads Base Specifications Detector SpecificationsElectrical Supervision Mount the Bases Install the BasesEOL Resistors Wire the BasesLoop Wiring Specifications Terminal ConnectionsFour-wire Loop Termination Wire Optional Remote AnnunciatorsWire F220-B6C/E/R Four-wire Bases Wire F220-B6 Two-wire Bases2 F220-B6E 1 F220-B6CF220-B6E F220-B6R 3 F220-B6RWire Power Supervision Modules Wire F220-B6E Power Supervision BaseWire D275 Power Supervision Module Install the Detector Heads Mount the Detector HeadsOptional Locking Bar LED Mounting SkirtKeyed. Do not force them onto the mounting bases Detector HeadTest Mode Sensitivity ModeSet Detector Modes Flash Rate and Trouble Indication Set CleanMe FeatureInspect the Installation Test the InstallationActivate an Alarm at Each Detector Reset the Control PanelTest Each Detector Test the Alarm Loop Perform Nfpa 72 Required TestingTest CO Sensors Page Page USA