24 en Test the Installation

F220 Series Detectors with F220-B6/C/E/R Bases

 

 

every eight seconds. This verifies the detector is receiving power and operating properly.

NOTE! If a heat detector LED flashes at a rate of

4 flashes/sec, the detector is either cold (below +32°F

i [0°C]), out of sensitivity range, or defective. If a smoke detector flashes at a rate of 4 flashes/sec, it is either out of sensitivity range or defective.

5.2Test Each Detector

Test each detector to ensure it causes a control panel alarm. Reset the control panel after each test.

5.2.1Activate an Alarm at Each Detector

To cause heat detectors to alarm either:

Activate the internal reed switch by placing a magnet horizontally against the T mark on the mounting skirt (refer to Figure 4.2, Item 8 on page 19) and holding it there for three consecutive LED flashes, or

Expose the thermistor (refer to Figure 2.2, Item 3 on page 7)to a heat source such as a hair dryer or a shielded

heat lamp until the detector alarms and the alarm LED lights .

To cause smoke detectors to alarm either:

Activate the internal reed switch by placing a magnet horizontally against the T mark on the mounting skirt (refer to Figure 4.2, Item 8 on page 19) and holding it there for three consecutive LED flashes, or

Use a UL Listed aerosol smoke detector tester to simulate an alarm. Follow the instructions provided with the aerosol smoke detector tester.

5.2.2Reset the Control Panel

When a detector alarms, the red LED indicator activates and latches into the ON position. Clear the alarm by momentarily removing power before proceeding to the next detector.

4998138694 -04 2007.01

Installation Manual

Bosch Security Systems, Inc.

Image 24
Contents F220 Series Detectors with F220-B6/C/E/R Bases Required Maintenance and Testing LegalTrademarks General Information F220-B6 Series Detector BasesCompatible Control Panels Base Comparisons Base Features F220 Series Detectors About F220 Series Detector Heads2 F220 Series Detector Features 3 F220 Series Heat Detector HeadsTechnical Specifications General Specifications4 F220 Series Smoke Detector Heads Base Specifications Detector SpecificationsElectrical Supervision Install the Bases Mount the BasesWire the Bases Loop Wiring SpecificationsTerminal Connections EOL ResistorsWire Optional Remote Annunciators Four-wire Loop TerminationWire F220-B6 Two-wire Bases Wire F220-B6C/E/R Four-wire Bases1 F220-B6C 2 F220-B6EF220-B6E 3 F220-B6R F220-B6RWire Power Supervision Modules Wire F220-B6E Power Supervision BaseWire D275 Power Supervision Module Install the Detector Heads Mount the Detector HeadsOptional Locking Bar Mounting Skirt LEDDetector Head Keyed. Do not force them onto the mounting basesTest Mode Sensitivity ModeSet Detector Modes Set CleanMe Feature Flash Rate and Trouble IndicationTest the Installation Inspect the InstallationActivate an Alarm at Each Detector Reset the Control PanelTest Each Detector Test the Alarm Loop Perform Nfpa 72 Required TestingTest CO Sensors Page Page USA