Bosch Appliances F220-B6 Set CleanMe Feature, Flash Rate and Trouble Indication

Page 22

22 en Install the Detector Heads

F220 Series Detectors with F220-B6/C/E/R Bases

 

 

4.3Set CleanMe Feature

The Clean Me feature monitors the smoke chamber’s sensitivity and sends a trouble signal to the control panel when the sensitivity degrades to a preset level.

NOTE! When a CleanMe signal is sent to a control panel

i that is not CleanMe compatible, the signal may be misinterpreted as an alarm.

To activate the CleanMe feature:

1.Put the detector into sensitivity mode by placing a magnet next to the T mark on the mounting skirt (refer to Figure 4.2, Item 8 on page 19). Remove the magnet after the first red LED flash and before the third red LED flash.

2.When the magnet is removed, the LED flashes green once and shows the first of two sensitivity displays.

3.When the LED next flashes red, replace the magnet near the T mark(refer to Figure 4.2, Item 8 on page 19).

4.Hold the magnet against the T mark on the mounting skirt (refer to Figure 4.2, Item 8 on page 19) until the green LED flashes twice and the red LED repeats the sensitivity indication.

5.The detector exits sensitivity mode. If CleanMe has been successfully enabled, the green LED flashes twice in rapid

succession every eight seconds indicating that CleanMe is activated.

To disable CleanMe, repeat this process and verify the double flash returns to a single flash.

4.4Flash Rate and Trouble Indication

These detectors include the Chamber Check Automatic Trouble Indicator that verifies the detector’s calibration is within the factory listed range. NFPA guidelines for sensitivity testing can be met by visually inspecting the detector and checking the flash rate of the LED.

4998138694 -04 2007.01

Installation Manual

Bosch Security Systems, Inc.

Image 22
Contents F220 Series Detectors with F220-B6/C/E/R Bases Legal Required Maintenance and TestingTrademarks F220-B6 Series Detector Bases General InformationCompatible Control Panels Base Comparisons Base Features F220 Series Detectors About F220 Series Detector Heads2 F220 Series Detector Features 3 F220 Series Heat Detector HeadsGeneral Specifications Technical Specifications4 F220 Series Smoke Detector Heads Detector Specifications Base SpecificationsElectrical Supervision Install the Bases Mount the BasesTerminal Connections Wire the BasesLoop Wiring Specifications EOL ResistorsWire Optional Remote Annunciators Four-wire Loop TerminationWire F220-B6 Two-wire Bases Wire F220-B6C/E/R Four-wire Bases1 F220-B6C 2 F220-B6EF220-B6E 3 F220-B6R F220-B6RWire F220-B6E Power Supervision Base Wire Power Supervision ModulesWire D275 Power Supervision Module Mount the Detector Heads Install the Detector HeadsOptional Locking Bar Mounting Skirt LEDDetector Head Keyed. Do not force them onto the mounting basesSensitivity Mode Test ModeSet Detector Modes Set CleanMe Feature Flash Rate and Trouble IndicationTest the Installation Inspect the InstallationReset the Control Panel Activate an Alarm at Each DetectorTest Each Detector Perform Nfpa 72 Required Testing Test the Alarm LoopTest CO Sensors Page Page USA