Bosch Appliances F220-B6 installation manual Test the Installation, Inspect the Installation

Page 23

F220 Series Detectors with F220-B6/C/E/R Bases

Test the Installation en 23

 

 

NOTE! Perform the visual check before resetting power.

i After a reset the trouble indicators clear for 70 seconds. After 70 seconds, if the detector is in a trouble condition, trouble indications begin again.

A unit with CleanMe activated double flashes (two flashes within a half second of each other) every eight seconds. A normally operating unit flashes once every eight seconds. If a detector is in a trouble condition due to a dirty lens or a sensor malfunction, it single or double flashes every four seconds. If enabled, the CleanMe trouble signal is sent.

5 Test the Installation

5.1Inspect the Installation

1.Check the wiring from the control panel to the last head on each run for proper polarity and continuity.

2.Terminate each run with an EOL resistor as specified by the control panel manufacturer.

3.Terminate four-wire runs with EOL power supervision modules or F220-B6E bases.

4.Apply power to the system. Check for alarms and troubles.

5.Note which detectors alarmed (if any), shut down the system, remove alarmed detectors from their bases, and recheck the bases for proper wiring.

6.If the problem persists, determine if the problem is caused by the detector or the base. Replace the affected detectors or bases with known good units.

7.If a system alarm occurs with no detector alarms present, remove all detectors and check the wiring at each base.

8.Check the wiring of each EOL resistor and EOL module.

9.When the system is alarm free, check each detector to ensure that the green LED indicator flashes approximately

Bosch Security Systems, Inc.

Installation Manual

4998138694 -04 2007.01

Image 23
Contents F220 Series Detectors with F220-B6/C/E/R Bases Trademarks Required Maintenance and TestingLegal Compatible Control Panels General InformationF220-B6 Series Detector Bases Base Comparisons Base Features About F220 Series Detector Heads F220 Series Detectors3 F220 Series Heat Detector Heads 2 F220 Series Detector Features4 F220 Series Smoke Detector Heads Technical SpecificationsGeneral Specifications Electrical Supervision Base SpecificationsDetector Specifications Mount the Bases Install the BasesEOL Resistors Wire the BasesLoop Wiring Specifications Terminal ConnectionsFour-wire Loop Termination Wire Optional Remote AnnunciatorsWire F220-B6C/E/R Four-wire Bases Wire F220-B6 Two-wire Bases2 F220-B6E 1 F220-B6CF220-B6E F220-B6R 3 F220-B6RWire D275 Power Supervision Module Wire Power Supervision ModulesWire F220-B6E Power Supervision Base Optional Locking Bar Install the Detector HeadsMount the Detector Heads LED Mounting SkirtKeyed. Do not force them onto the mounting bases Detector HeadSet Detector Modes Test ModeSensitivity Mode Flash Rate and Trouble Indication Set CleanMe FeatureInspect the Installation Test the InstallationTest Each Detector Activate an Alarm at Each DetectorReset the Control Panel Test CO Sensors Test the Alarm LoopPerform Nfpa 72 Required Testing Page Page USA