2 en Legal

F220 Series Detectors with F220-B6/C/E/R Bases

 

 

1 Legal

1.1Trademarks

CleanMe® is a registered trademark of GE Interlogix in the United States and/or other countries.

Chamber Check® is a registered trademark of Bosch Security Systems, Inc. in the United States.

Chambermaid™ is a trademark of Bosch Security Systems, Inc. in the United States.

ENVI-RO-TECH™ is a trademark of Tech Spray L.P.

TECHSPRAY® is a registered trademark of Tech Spray L.P.

1.2Required Maintenance and Testing

Keep the detector calibrated for proper operation. NFPA 72, The National Fire Alarm Code, recommends performing calibration tests at installation, then every other year. Depending on local regulations, calibration testing might be required more than once a year.

Perform functional testing yearly.

NOTE! Notify all concerned parties before any

i maintenance or testing of the fire alarm system and upon completion of these activities.

Test the calibration (to meet NFPA 72) using either the magnet test or measuring the calibration with a calibrated product from No Climb Products Ltd. Quickly determine the calibration by a visual inspection of the detector’s LED (refer to Section 4.4 Flash Rate and Trouble Indication on page 22). These tests confirm whether or not the detector is within its factory marked calibration range.

At least once a year vacuum or wipe the external part of the detector clean. Pay particular attention to the detector screens in areas of heavy insect activity or dust. To clean the chamber,

4998138694 -04 2007.01

Installation Manual

Bosch Security Systems, Inc.

Image 2
Contents F220 Series Detectors with F220-B6/C/E/R Bases Trademarks Required Maintenance and TestingLegal Compatible Control Panels General InformationF220-B6 Series Detector Bases Base Comparisons Base Features F220 Series Detectors About F220 Series Detector Heads2 F220 Series Detector Features 3 F220 Series Heat Detector Heads4 F220 Series Smoke Detector Heads Technical SpecificationsGeneral Specifications Electrical Supervision Base SpecificationsDetector Specifications Install the Bases Mount the BasesTerminal Connections Wire the BasesLoop Wiring Specifications EOL ResistorsWire Optional Remote Annunciators Four-wire Loop TerminationWire F220-B6 Two-wire Bases Wire F220-B6C/E/R Four-wire Bases1 F220-B6C 2 F220-B6EF220-B6E 3 F220-B6R F220-B6RWire D275 Power Supervision Module Wire Power Supervision ModulesWire F220-B6E Power Supervision Base Optional Locking Bar Install the Detector HeadsMount the Detector Heads Mounting Skirt LEDDetector Head Keyed. Do not force them onto the mounting basesSet Detector Modes Test ModeSensitivity Mode Set CleanMe Feature Flash Rate and Trouble IndicationTest the Installation Inspect the InstallationTest Each Detector Activate an Alarm at Each DetectorReset the Control Panel Test CO Sensors Test the Alarm LoopPerform Nfpa 72 Required Testing Page Page USA