F220 Series Detectors with F220-B6/C/E/R Bases

Install the Bases en 11

 

 

3.2Wire the Bases

CAUTION! When wiring bases, all terminal screws

!including those not wired must be tightened to prevent loose screw heads from making intermitent electrical

contact with the detector head.

3.2.1Terminal Connections

WARNING! Do not twist or loop the wires around the terminals. In and out wires for terminal connection must

!be cut, stripped, and inserted as individual ends.

NOTE! Bring the positive (+) wires in on terminal b2 and

i out from terminal b1. Use a consistent pattern, inputting on b2 and outputting from b1. The negative (-) wires input and output from the same terminal (a1/a2).

3.2.2EOL Resistors

Use the EOL resistors supplied or specified by the control panel manufacturer. This applies to all loop terminations including the D275 Module and the F220-B6E Power Supervision Base.

3.2.3Loop Wiring Specifications

In a two-wire system, the maximum loop length depends on the number of F220-B6 bases on the loop, the wire size, and the control panel specifications. Refer to the control panel's installation instructions for specific wiring information.

In a four-wire system, the maximum loop length and number of bases that can be placed on a loop depend on the voltage drop on the power circuit. Use standard voltage drop calculations to ensure that the last detector on the loop meets the minimum voltage requirement of at least 10 V.

Bosch Security Systems, Inc.

Installation Manual

4998138694 -04 2007.01

Image 11
Contents F220 Series Detectors with F220-B6/C/E/R Bases Trademarks Required Maintenance and TestingLegal Compatible Control Panels General InformationF220-B6 Series Detector Bases Base Comparisons Base Features About F220 Series Detector Heads F220 Series Detectors3 F220 Series Heat Detector Heads 2 F220 Series Detector Features 4 F220 Series Smoke Detector Heads Technical Specifications General Specifications Electrical Supervision Base SpecificationsDetector Specifications Mount the Bases Install the BasesEOL Resistors Wire the BasesLoop Wiring Specifications Terminal ConnectionsFour-wire Loop Termination Wire Optional Remote AnnunciatorsWire F220-B6C/E/R Four-wire Bases Wire F220-B6 Two-wire Bases2 F220-B6E 1 F220-B6CF220-B6E F220-B6R 3 F220-B6RWire D275 Power Supervision Module Wire Power Supervision ModulesWire F220-B6E Power Supervision Base Optional Locking Bar Install the Detector HeadsMount the Detector Heads LED Mounting SkirtKeyed. Do not force them onto the mounting bases Detector HeadSet Detector Modes Test ModeSensitivity Mode Flash Rate and Trouble Indication Set CleanMe FeatureInspect the Installation Test the InstallationTest Each Detector Activate an Alarm at Each DetectorReset the Control Panel Test CO Sensors Test the Alarm LoopPerform Nfpa 72 Required Testing Page Page USA