Bosch Appliances F220-B6 Electrical Supervision, Base Specifications, Detector Specifications

Page 9

F220 Series Detectors with F220-B6/C/E/R BasesGeneral Information en 9

2.3.2

Base Specifications

 

 

 

 

 

Alarm Current (only base current, detector current excluded)

 

 

 

 

F220-B6:

Two-wire base; no base current

 

 

 

 

F220-B6C:

31 mA at 12 VDC

 

 

35 mA at 24 VDC

 

 

40 mA maximum at 30 VDC

 

 

 

 

F220-B6E:

25 mA at 12 VDC

 

 

30 mA at 24 VDC

 

 

34 mA maximum at 30 VDC

 

 

 

 

F220-B6R:

13.5 mA at 12 VDC

 

 

16.5 mA at 24 VDC

 

 

19 mA maximum at 30 VDC

 

 

 

 

Standby Current

 

 

 

 

 

F220-B6/C/R:

No current draw in standby

 

 

 

 

F220-B6E:

16 mA maximum at 30 VDC

 

 

 

 

Voltage

 

 

 

 

 

F220-B6 (two-wire):

8.5 VDC to 32.0 VDC

 

 

 

 

F220-B6C/E/R (four-wire):

10.0 VDC to 30.0 VDC

 

 

 

 

Table 2.4 F220-B6 Series Base Specifications

2.3.3Detector Specifications

Current

Alarm:

20 mA minimum at 8.5 VDC

 

35 mA maximum at 32 VDC

 

 

Standby:

0.12 mA maximum

 

 

Startup:

0.12 mA maximum

 

 

Powerup Time

22 second maximum

 

 

Rate of Rise

 

 

 

F220-135:

15°F/min (9°C/min) or greater

 

 

Voltage

 

 

 

Operating:

8.5 VDC to 32.0 VDC

 

 

RMS Ripple:

25% of DC input

 

 

Table 2.5 F220 Series Detector Heads Specifications

2.4Electrical Supervision

When the F220-B6 Series Bases are wired according to the instructions in this document, the control panel initiates a trouble signal when a detector is removed from its base,

Bosch Security Systems, Inc.

Installation Manual

4998138694 -04 2007.01

Image 9
Contents F220 Series Detectors with F220-B6/C/E/R Bases Required Maintenance and Testing LegalTrademarks General Information F220-B6 Series Detector BasesCompatible Control Panels Base Comparisons Base Features About F220 Series Detector Heads F220 Series Detectors3 F220 Series Heat Detector Heads 2 F220 Series Detector FeaturesTechnical Specifications General Specifications4 F220 Series Smoke Detector Heads Base Specifications Detector SpecificationsElectrical Supervision Mount the Bases Install the BasesLoop Wiring Specifications Wire the BasesTerminal Connections EOL ResistorsFour-wire Loop Termination Wire Optional Remote AnnunciatorsWire F220-B6C/E/R Four-wire Bases Wire F220-B6 Two-wire Bases2 F220-B6E 1 F220-B6CF220-B6E F220-B6R 3 F220-B6RWire Power Supervision Modules Wire F220-B6E Power Supervision BaseWire D275 Power Supervision Module Install the Detector Heads Mount the Detector HeadsOptional Locking Bar LED Mounting SkirtKeyed. Do not force them onto the mounting bases Detector HeadTest Mode Sensitivity ModeSet Detector Modes Flash Rate and Trouble Indication Set CleanMe FeatureInspect the Installation Test the InstallationActivate an Alarm at Each Detector Reset the Control PanelTest Each Detector Test the Alarm Loop Perform Nfpa 72 Required TestingTest CO Sensors Page Page USA