F220 Series Detectors with
2.3.2 | Base Specifications |
|
|
|
|
| Alarm Current (only base current, detector current excluded) | |
|
|
|
| ||
|
|
|
| 31 mA at 12 VDC | |
|
| 35 mA at 24 VDC |
|
| 40 mA maximum at 30 VDC |
|
|
|
| 25 mA at 12 VDC | |
|
| 30 mA at 24 VDC |
|
| 34 mA maximum at 30 VDC |
|
|
|
| 13.5 mA at 12 VDC | |
|
| 16.5 mA at 24 VDC |
|
| 19 mA maximum at 30 VDC |
|
|
|
| Standby Current |
|
|
|
|
| No current draw in standby | |
|
|
|
| 16 mA maximum at 30 VDC | |
|
|
|
| Voltage |
|
|
|
|
| 8.5 VDC to 32.0 VDC | |
|
|
|
| 10.0 VDC to 30.0 VDC | |
|
|
|
| Table 2.4 |
2.3.3Detector Specifications
Current
Alarm: | 20 mA minimum at 8.5 VDC |
| 35 mA maximum at 32 VDC |
|
|
Standby: | 0.12 mA maximum |
|
|
Startup: | 0.12 mA maximum |
|
|
Powerup Time | 22 second maximum |
|
|
Rate of Rise |
|
|
|
15°F/min (9°C/min) or greater | |
|
|
Voltage |
|
|
|
Operating: | 8.5 VDC to 32.0 VDC |
|
|
RMS Ripple: | 25% of DC input |
|
|
Table 2.5 F220 Series Detector Heads Specifications
2.4Electrical Supervision
When the
Bosch Security Systems, Inc. | Installation Manual | 4998138694 |