8 en General Information

F220 Series Detectors with F220-B6/C/E/R Bases

 

 

2.2.4F220 Series Smoke Detector Heads

The F220 Series Smoke Detector Heads are UL Listed, open- area photoelectric smoke detectors that work with commercial fire protective signaling systems and household fire warning systems. Select the appropriate mounting base to configure the detectors for two-wire or four-wire versions (refer to

Section 2.1.2 Base Comparisons on page 4).

To verify power to the detector and a functioning smoke sampling circuitry, a dual color LED indicator flashes green every eight seconds when operating normally. It flashes once every four seconds when a trouble condition exists. If the detector determines an alarm condition exists, the LED changes from flashing green to steady red. The detector returns to normal when power is interrupted and the alarm condition clears.

Throughout its normal life cycle, the smoke detector monitors and periodically adjusts itself to keep the sensitivity at its factory calibrated level. When excessively dirty, the detector’s LED flash rate changes from an eight second flash rate to a four second rate. If CleanMe is selected, the detector sends a CleanMe signal to the compatible control panel to indicate a dirty smoke detector.

Refer to Section 4.3 Set CleanMe Feature on page 22.

2.3Technical Specifications

2.3.1General Specifications

Air Velocity

4000 ft/min (1200 m/min) maximum

 

 

Operating

+32°F to 100°F (0°C to 38°C)

Temperature

 

 

 

Relative

0% to 95% (non-condensing)

Humidity

 

 

 

Table 2.3 Specifications - Detectors and Bases

4998138694 -04 2007.01

Installation Manual

Bosch Security Systems, Inc.

Image 8
Contents F220 Series Detectors with F220-B6/C/E/R Bases Trademarks Required Maintenance and TestingLegal Compatible Control Panels General InformationF220-B6 Series Detector Bases Base Comparisons Base Features F220 Series Detectors About F220 Series Detector Heads2 F220 Series Detector Features 3 F220 Series Heat Detector Heads4 F220 Series Smoke Detector Heads Technical SpecificationsGeneral Specifications Electrical Supervision Base SpecificationsDetector Specifications Install the Bases Mount the BasesWire the Bases Loop Wiring SpecificationsTerminal Connections EOL ResistorsWire Optional Remote Annunciators Four-wire Loop TerminationWire F220-B6 Two-wire Bases Wire F220-B6C/E/R Four-wire Bases1 F220-B6C 2 F220-B6EF220-B6E 3 F220-B6R F220-B6RWire D275 Power Supervision Module Wire Power Supervision ModulesWire F220-B6E Power Supervision Base Optional Locking Bar Install the Detector HeadsMount the Detector Heads Mounting Skirt LEDDetector Head Keyed. Do not force them onto the mounting basesSet Detector Modes Test ModeSensitivity Mode Set CleanMe Feature Flash Rate and Trouble IndicationTest the Installation Inspect the InstallationTest Each Detector Activate an Alarm at Each DetectorReset the Control Panel Test CO Sensors Test the Alarm LoopPerform Nfpa 72 Required Testing Page Page USA