4 Termination Locations
A. Appliance Opening Minimum Clearances
WARNING
Fire Risk. Explosion Risk.
Maintain vent termination minimum clearances as specified.
= AREA WHERE APPLIANCE IS NOT PERMITTED
D
E
G
FP
A H
X= AIR SUPPLY INLET
FP = APPLIANCE OPENING
M |
L
B
B |
FP |
F FP |
FP |
| B |
|
| |
| FP | I |
|
| |
|
| A |
R
M
FP X
J or K
P |
N |
FP |
Q |
(See Note 2)
A | = | 0” | clearances above grade, veran- |
|
| (See Note 1) | da, porch, deck or balcony |
B* | = | 12” | clearances to window or door |
|
|
| that may be opened, or to per- |
|
|
| manently closed window. |
D | = |
| vertical clearance to ventilated |
|
| soffit located above the hood | |
|
|
| within a horizontal distance of 2 |
|
|
| feet (60 cm) from the |
|
|
| |
|
|
| of the hood |
E | = | .. .clearance to unventilated soffit | |
|
|
| |
F | = | 9” | clearance to outside corner |
G* | = | 12” | clearance to inside corner |
H | = | 3 ft. (Canada) | not to be installed above a gas me- |
|
|
| ter/regulator assembly within 3 feet |
|
|
| (90cm) horizontally from the center- |
|
|
| line of the regulator |
I | = | 3 ft | clearance to service regulator vent |
|
|
| outlet and electric service |
*36” minimum for vinyl windows or vinyl siding.
**a appliance shall not open directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.
***only permitted if veranda, porch, deck or balcony is fully open on a minimum of 2 sides beneath the floor, or if the screened porch guidelines are followed.
NOTE 1: Local codes or regulations may require different clearances.
NOTE 2: Termination in an alcove space (spaces open only on one side and with an overhang) are permitted with the dimensions specified for vinyl or
Figure 4.1 Minimum Clearances for Appliance Opening
J | = | 9” (U.S.A.) |
|
|
|
|
|
|
| 12” (Canada) | clearance to |
| |||
|
|
| cal air supply inlet to building |
| |||
|
|
| or the combustion air inlet to |
| |||
K | = | 3 ft. (U.S.A.) | any other appliance |
| |||
|
|
|
|
| |||
|
| 6 ft. (Canada) | clearance | to a mechanical |
| ||
|
|
| air supply inlet |
| |||
L** | = | 54” | clearance above paved side- |
| |||
|
| (See Note 1) | walk or a paved driveway lo- |
| |||
|
|
| cated on public property |
| |||
M***= | clearance | under veranda, |
| ||||
|
|
| porch, deck, balcony or over- |
| |||
|
|
| hang |
|
|
| |
|
|
| vinyl |
|
|
| |
N | = | 12” |
|
| |||
|
| 36” | vinyl siding |
|
|
| |
P | = | 8 ft. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| QMIN |
| RMAX |
|
| 10 feet |
| 2 x Q ACTUAL |
| |||
1 additional termination cap |
| Q + 3 feet |
| 1 x Q ACTUAL |
| ||
2 additional termination caps |
| Q + 6 feet |
| 2/3 x Q ACTUAL |
| ||
3 additional termination caps |
| Q + 9 feet |
| 1/2 x Q ACTUAL |
| ||
|
| RMAX = (2 / # caps plus appliance) x QACTUAL |
|
This appliance is approved for installation onto screened porches with the following guidelines:
Minimum porch area: 96 square feet
Minimum ceiling height: 92 inches Minimum two walls must be screened
Minimum top of screen height, side walls: 6 ft. 8 in.
Minimum screen area: 64 square feet
NOTE: There may be some odor and small amounts of soot associated with venting the
10 | Heat & Glo LifeStyle Collection • |