Emerson Process Management CI-9110, Series 9110 Input Filter, Switch SW1 1-5, Pulse Increments

Page 28

The relationship between an ON and OFF pulse time periods are shown by the following two equations:

1)T on Minimum (sec.) = (.01 SR) + K

2)T off Minimum (sec.) = K

Where:

 

 

T on Minimum =

Raise, Lower or Guard pulse

T off Minimum =

Time between pulses.

S

=

Incremental step value (Table 3-2)

R

=

Rate of output change (Table 3-3)

K= .04 sec. with R/L filter active or 0.01 sec. with R/L filter turned off. See Section 3.6 - "Output Rate of Change."

Table 3-2 - Switch SW1 (1-5), Pulse Increments

 

SW1-5

 

 

SW1-4

 

 

SW1-3

 

 

SW1-2

 

SW1-1

 

Output Change

 

 

 

 

 

 

 

 

 

 

(nominal, ±15%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Close

Close

Close

Close

Close

Disabled

 

Close

Close

Open

Open

Close

0.110% / Pulse

 

Open

Close

Close

Close

Open

0.182% / Pulse

 

Open

Close

Close

Open

Close

0.365% / Pulse

 

Open

Close

Open

Close

Close

0.730% / Pulse

 

Open

Close

Open

Open

Close

1.090% / Pulse

 

Open

Close

Open

Open

Open

1.280% / Pulse

 

Open

Open

Close

Close

Close

1.460% / Pulse

 

Open

Open

Close

Close

Open

1.640% / Pulse

 

Open

Open

Close

Open

Close

1.830% / Pulse

 

Open

 

Open

Open

Open

Open

Continuous *

*Analog Regulator models must always have these switches set for Continuous Mode.

3.4 INPUT FILTER

A raise or lower input signal can contain noise pulses of an amplitude sufficient to affect the output. In these situations, switch SW1-8 can be set to activate an input filter. The switch positions are given below. For Analog models, this switch must always be set to OPEN.

SW1-8 Filter Status

Close Active

Open Inactive

Board Setup

3-4

CI-9110

Image 28
Contents Remote Set Regulator Model 9110-00A IMPORTANT! Read Instructions Before Starting Warranty Bristol Inc MailPhone Bristol Inc. Repair Authorization Form off-line completion Training Telephone Support Technical Questions 860 860 945-2213 FAXVisit our Site on the World Wide Web Training Courses Model 9110-00A Remote SET Regulator Supplemental Instructions Theory of Operation Product DescriptionAnalog Regulator Model Remote Set Regulator Block Diagram of Analog Type Regulator Guard Input Current OutputBlock Diagram of Raise/Lower Type Regulator Raise/Lower Regulator Model Data PlateModel Number Breakdown = Pneumatic Output = Mounting Arrangement Page General MountingTwo-Inch Pipe Mounting In-Line MountingPressure Connections General PipingRegulator Assembly Moisture in LinesInternal Access Line SizeVenting Body and CoverSafety Note Electrical Conduit PortPage Cradle Switches with Open Designation Using Option SwitchesSlide Switches with on Designation Switch Functions Regulator Assembly Switch SW1 & SW2 Functions & SettingsAnalog Input Models RAISE/LOWER Input ModelsContinuous Signal Incremental SignalSwitch SW1 1-5, Pulse Increments Input FilterGuard Input Output Rate of ChangeStatic or Dynamic Guard Input Guard LogicSwitch SW2 2-5, Output Rate Of Change Analog Failure Modes Fail Hold & Fail ZeroFAIL-ZERO Mode Page Field Wiring Terminal Identification For Analog Input Models Terminal Identification For Raise/Lower ModelsAnalog Voltage Input with Guard Analog Current Input 4-20 mA with Guard RAISE/LOWER Inputs with GuardRaise/Lower & Guard Inputs from Relay Contacts DC Power Current Output to FSK Bi-State TransmitterOperating Notes Initial ChecksField Wiring CI-9110 Service Troubleshooting Hints Setting Output Limits Test SetupProcedure General PrinciplesCalibration Test Setup Calibration PrecautionAnalog Test Setup Preliminary Calibration CheckDetailed Calibration for Analog Model Feedback Zero & SpanCurrent Output Span & Load Pressure Output CheckRaise/Lower Test Setup Detailed Calibration for RAISE/LOWER ModelPCB Reference Drawings CPU Board & Termination Board Reference TableAssembly, Analog Type CPU Board with Current Output Assembly, Raise/Lower Type CPU Board with Current Output Analog Input Model RAISE/LOWER Input ModelAnalog Output Accuracy Analog ModelsAccuracy RAISE/LOWER Models Stepper Drive MechanismPressure Regulator Assembly Instrument EnclosureEnvironmental Range Factory Calibrated withHumidity 10 to 95% over -20to +130 F -29to +55 Range Model 9110 Main Parts Parts Referenced in FigureRemote Set Regulator Actuator Unit Remote Set Regulator Actuator Unit Mounting Parts Remote Set Regulator Assembly Basic Parts Remote SET Regulator Basic PartsGuidelines for System Grounding Basic Ground Rod Installation Noise and Signal Errors General RecommendationsGrounding of Equipment Housing Transients and Interference Grounding of Transmitter Types of Earth Grounds AC Power Grounding System Sandy Soil Dry SoilRocky Soil Several DPCs Mounted in Metal Cabinet with Power Supply Following installation procedures applyGrounding for DPCs and Power Supplies Single Metal Cabinet Multiple DPC Cabinets Powered by Single Power Supply Elements of a Facility Ground System Multiple Clusters of DPC Cabinets Powered by Local Supplies ReferencesPage Remote Set Regulator Model 9110-00A