5.If the output pressure of the Remote Set Regulator fails to change even with a change at the Command input, the internal fuse may be blown. Check and replace it as required with a 1A, 250V 3AG type. If the fuse continues to blow, check for wiring mistakes at the field wiring terminals or check for a defective PC board. Do not attempt further operation until the problem has been resolved.
6.Once all the above checks have been completed, turn on the associated process and verify that the Regulator is operating properly. Startup is complete.
Field Wiring |
|