Emerson Process Management Series 9110, CI-9110, 9110-00A Analog Current Input 4-20 mA with Guard

Page 36

For the application of Figure 4-2, the Carrier Presence output signal of the receiver may be connected to the Guard terminal as shown. Should the tone carrier fail, the Regulator will hold the last valid output value and prevent the Command Input from responding to extraneous signals.

4.4 ANALOG CURRENT INPUT (4-20 mA) WITH GUARD

In Figure 4-3, a 4-20 mA signal is obtained from the collector of an output transistor and wired to the input of the Regulator. Switch SW2-8 is set to the CLOSE position to bring the loop resistor into the circuit. The equivalent 1-5 volt drop across the 250 ohm loop resistor provides the Regulator input.

A switch or contact signal may be wired to the Guard Terminal as shown in Figure 4-3. This signal will be in an ON state when valid command data is sent and in an OFF state if the telemetry link opens.

The Guard signal may also emanate from an open collector circuit such as shown in Figure 4-2

4.5 RAISE/LOWER INPUTS WITH GUARD

The Raise and Lower inputs will accept either a continuous or incremental signal. A continuous signal is one that is held in a TRUE state to obtain a change of output pressure. An incremental signal is one that produces a step change of the output value for each TRUE input pulse that is received. Both types of inputs will maintain the last output value during the FALSE or failed states of the signal. The wiring illustrations described herein are applicable to either type.

The Guard input performs the same function as described under the previous analog subtopics. Since the Guard input is electrically identical to the Raise and Lower inputs, it can be wired in the same manner.

Figure 4-4 shows all inputs wired to external relay contacts or switches. Each contact is wired to a positive voltage source which must have the same value as the supply voltage required to power the Regulator (12 or 24 V type). When a contact is closed, the input is set ON (TRUE). When a contact is open, it is set OFF (FALSE).

The arrangement of Figure 4-5 receives all three inputs from a METATONE B FSK Tri- State Receiver. This receiver provides a MARK and SPACE output which connect to the respective Raise and Lower input terminals, and a CARRIER output that connects to the Guard terminal. The Receiver's tri-state outputs are provided as open collectors that drive the opto-isolated inputs of the Regulator. When any of the receiver's driver transistors conduct, the corresponding Regulator input will be set TRUE. When any driver transistor is cut off, the corresponding Regulator input will be set FALSE.

Field Wiring

4-4

CI-9110

Image 36
Contents Remote Set Regulator Model 9110-00A IMPORTANT! Read Instructions Before Starting Warranty Mail Bristol IncPhone Bristol Inc. Repair Authorization Form off-line completion Training Telephone Support Technical Questions 860 860 945-2213 FAXVisit our Site on the World Wide Web Training Courses Model 9110-00A Remote SET Regulator Supplemental Instructions Product Description Theory of OperationAnalog Regulator Model Remote Set Regulator Block Diagram of Analog Type Regulator Guard Input Current OutputBlock Diagram of Raise/Lower Type Regulator Data Plate Raise/Lower Regulator ModelModel Number Breakdown = Pneumatic Output = Mounting Arrangement Page General MountingTwo-Inch Pipe Mounting In-Line MountingPressure Connections General PipingRegulator Assembly Moisture in LinesInternal Access Line SizeVenting Body and CoverSafety Note Electrical Conduit PortPage Using Option Switches Cradle Switches with Open DesignationSlide Switches with on Designation Switch Functions Regulator Assembly Switch SW1 & SW2 Functions & SettingsAnalog Input Models RAISE/LOWER Input ModelsContinuous Signal Incremental SignalSwitch SW1 1-5, Pulse Increments Input FilterGuard Input Output Rate of ChangeStatic or Dynamic Guard Input Guard LogicSwitch SW2 2-5, Output Rate Of Change Analog Failure Modes Fail Hold & Fail ZeroFAIL-ZERO Mode Page Field Wiring Terminal Identification For Analog Input Models Terminal Identification For Raise/Lower ModelsAnalog Voltage Input with Guard Analog Current Input 4-20 mA with Guard RAISE/LOWER Inputs with GuardRaise/Lower & Guard Inputs from Relay Contacts DC Power Current Output to FSK Bi-State TransmitterOperating Notes Initial ChecksField Wiring CI-9110 Service Troubleshooting Hints Setting Output Limits Test SetupProcedure General PrinciplesCalibration Test Setup Calibration PrecautionAnalog Test Setup Preliminary Calibration CheckDetailed Calibration for Analog Model Feedback Zero & SpanCurrent Output Span & Load Pressure Output CheckRaise/Lower Test Setup Detailed Calibration for RAISE/LOWER ModelPCB Reference Drawings CPU Board & Termination Board Reference TableAssembly, Analog Type CPU Board with Current Output Assembly, Raise/Lower Type CPU Board with Current Output Analog Input Model RAISE/LOWER Input ModelAnalog Output Accuracy Analog ModelsAccuracy RAISE/LOWER Models Stepper Drive MechanismPressure Regulator Assembly Instrument EnclosureEnvironmental Range Factory Calibrated withHumidity 10 to 95% over -20to +130 F -29to +55 Range Model 9110 Main Parts Parts Referenced in FigureRemote Set Regulator Actuator Unit Remote Set Regulator Actuator Unit Mounting Parts Remote Set Regulator Assembly Basic Parts Remote SET Regulator Basic PartsGuidelines for System Grounding Basic Ground Rod Installation Noise and Signal Errors General RecommendationsGrounding of Equipment Housing Transients and Interference Grounding of Transmitter Types of Earth Grounds AC Power Grounding System Dry Soil Sandy SoilRocky Soil Several DPCs Mounted in Metal Cabinet with Power Supply Following installation procedures applyGrounding for DPCs and Power Supplies Single Metal Cabinet Multiple DPC Cabinets Powered by Single Power Supply Elements of a Facility Ground System Multiple Clusters of DPC Cabinets Powered by Local Supplies ReferencesPage Remote Set Regulator Model 9110-00A