Emerson Process Management 9110-00A, CI-9110 DC Power, Current Output to FSK Bi-State Transmitter

Page 38

CAUTION

When using the Regulator with a device that provides latching type outputs (output stays ON until turned OFF), the Raise/Lower inputs must be set for a pulse incremental signal. (see Section 3 - Board Setup). This will prevent the Regulator from driving full scale should the telemetry line open while in the middle of a Raise or Lower command. By using this configuration, the pressure output value will only change when input pulses are received.

Figure 4-6 - Current Output to FSK Bi-State Transmitter

4.6 4-20 mA CURENT OUTPUT

The current output of the Regulator can be used to drive a METATONE B, FSK Analog Transmitter as shown in Figure 4-6. The 4-20 mA current signal is referenced to signal common and flows through the loop resistor present at the input of the Analog Transmitter. The current signal modulates a tone carrier which communicates with an Analog Tone Receiver at the command site (not shown).

4.7 DC POWER

The Remote set Regulator is factory-shipped for 12 or 24 Vdc supply operation. Before power is applied, a check should be made to ensure that the Regulator type matches the supply source.

The dc supply source is wired to the Regulator in Figure 4-7. An earth ground must be provided for both the Regulator housing and the supply. The connection for the Regulator is made to the green grounding screw located inside the housing (see Section 2 - Installation for illustration).

WARNING

Metal enclosures and exposed metal parts of all electrical instruments and devices must be grounded to prevent accidental electrical shock. Grounding must be in accordance with latest OSHA rules and regulations pertaining to "Design Safety Standards For Electrical Systems."

Field Wiring

4-6

CI-9110

Image 38
Contents Remote Set Regulator Model 9110-00A IMPORTANT! Read Instructions Before Starting Warranty Phone MailBristol Inc Bristol Inc. Repair Authorization Form off-line completion Training Telephone Support Technical Questions 860 860 945-2213 FAXVisit our Site on the World Wide Web Training Courses Model 9110-00A Remote SET Regulator Supplemental Instructions Analog Regulator Model Product DescriptionTheory of Operation Remote Set Regulator Block Diagram of Analog Type Regulator Guard Input Current OutputBlock Diagram of Raise/Lower Type Regulator Model Number Breakdown Data PlateRaise/Lower Regulator Model = Pneumatic Output = Mounting Arrangement Page Two-Inch Pipe Mounting GeneralMounting In-Line MountingPressure Connections General PipingRegulator Assembly Moisture in LinesVenting Internal AccessLine Size Body and CoverSafety Note Electrical Conduit PortPage Slide Switches with on Designation Using Option SwitchesCradle Switches with Open Designation Analog Input Models Switch FunctionsRegulator Assembly Switch SW1 & SW2 Functions & Settings RAISE/LOWER Input ModelsContinuous Signal Incremental SignalSwitch SW1 1-5, Pulse Increments Input FilterStatic or Dynamic Guard Input Guard InputOutput Rate of Change Guard LogicSwitch SW2 2-5, Output Rate Of Change Analog Failure Modes Fail Hold & Fail ZeroFAIL-ZERO Mode Page Field Wiring Terminal Identification For Analog Input Models Terminal Identification For Raise/Lower ModelsAnalog Voltage Input with Guard Analog Current Input 4-20 mA with Guard RAISE/LOWER Inputs with GuardRaise/Lower & Guard Inputs from Relay Contacts DC Power Current Output to FSK Bi-State TransmitterOperating Notes Initial ChecksField Wiring CI-9110 Service Troubleshooting Hints Procedure Setting Output LimitsTest Setup General PrinciplesCalibration Test Setup Calibration PrecautionAnalog Test Setup Preliminary Calibration CheckCurrent Output Span & Load Detailed Calibration for Analog ModelFeedback Zero & Span Pressure Output CheckRaise/Lower Test Setup Detailed Calibration for RAISE/LOWER ModelPCB Reference Drawings CPU Board & Termination Board Reference TableAssembly, Analog Type CPU Board with Current Output Assembly, Raise/Lower Type CPU Board with Current Output Analog Input Model RAISE/LOWER Input ModelAccuracy RAISE/LOWER Models Analog OutputAccuracy Analog Models Stepper Drive MechanismEnvironmental Pressure Regulator AssemblyInstrument Enclosure Range Factory Calibrated withHumidity 10 to 95% over -20to +130 F -29to +55 Range Model 9110 Main Parts Parts Referenced in FigureRemote Set Regulator Actuator Unit Remote Set Regulator Actuator Unit Mounting Parts Remote Set Regulator Assembly Basic Parts Remote SET Regulator Basic PartsGuidelines for System Grounding Basic Ground Rod Installation Noise and Signal Errors General RecommendationsGrounding of Equipment Housing Transients and Interference Grounding of Transmitter Types of Earth Grounds AC Power Grounding System Rocky Soil Dry SoilSandy Soil Several DPCs Mounted in Metal Cabinet with Power Supply Following installation procedures applyGrounding for DPCs and Power Supplies Single Metal Cabinet Multiple DPC Cabinets Powered by Single Power Supply Elements of a Facility Ground System Multiple Clusters of DPC Cabinets Powered by Local Supplies ReferencesPage Remote Set Regulator Model 9110-00A