Emerson Process Management CI-9110 Detailed Calibration for Analog Model, Feedback Zero & Span

Page 46

5.If above readings are within stated specifications, stop! No calibration is required. Restore instrument to normal operation. Otherwise, proceed to topic 5.7 or 5.8 as required.

5.7 DETAILED CALIBRATION FOR ANALOG MODEL

If calibration errors were found in topic 5.6, the procedures described here for Analog models are performed.

5.7.1 Feedback Zero & Span

Precision voltage of an input test circuit is used to calibrate the zero and span as follows:

1.Adjust input test circuit for 1.000 V output.

2.DMM #1 should read 0.995 V, ±.004 V.

3.If reading of step 2 is out of tolerance, slightly loosen two screws on body of feedback pot (Figure 5-1) and rotate body until DMM #1 reads as specified in step 2. Secure pot screws to lock in setting.

4.Adjust the input test circuit for 5.000 V.

5.DMM #1 should read 4.995 V, ±.004 V

6.If the reading of step 5 is out of tolerance, adjust potentiometer R35 on CPU to correct.

7.Recheck both points and readjust zero and span if required.

5.7.2 Current Output Span & Load

The current output circuitry is provided with two calibration adjustments. Potentiometer R50 is used for span adjustment and R49 for load compensation. For these tests, DMM #2 (used as a milliammeter) is connected in series with a 250 ohm load resistor as shown in Figure 5-2. The pushbutton switch is used for load testing.

1.Adjust input test circuit for 5.000 V.

2.DMM #2 should read 20 mA, ±.02 mA. If necessary, adjust pot R50 to correct.

3.Press load pushbutton while observing DMM #2. If current reading increases, adjust R49 CCW. If reading decreases, turn it CW. Repeat procedure until change is less than

±.02 mA.

4.Final reading should be 20 mA, ±.02 mA. If necessary, reset pot R50 and repeat the procedure.

5.7.3 Pressure Output Check

1. Adjust input test circuit for 1.000 V.

Service

5-6

CI-9110

Image 46
Contents Remote Set Regulator Model 9110-00A IMPORTANT! Read Instructions Before Starting Warranty Bristol Inc MailPhone Bristol Inc. Repair Authorization Form off-line completion Training Telephone Support Technical Questions 860 860 945-2213 FAXVisit our Site on the World Wide Web Training Courses Model 9110-00A Remote SET Regulator Supplemental Instructions Theory of Operation Product DescriptionAnalog Regulator Model Remote Set Regulator Block Diagram of Analog Type Regulator Guard Input Current OutputBlock Diagram of Raise/Lower Type Regulator Raise/Lower Regulator Model Data PlateModel Number Breakdown = Pneumatic Output = Mounting Arrangement Page Two-Inch Pipe Mounting GeneralMounting In-Line MountingPressure Connections General PipingRegulator Assembly Moisture in LinesVenting Internal AccessLine Size Body and CoverSafety Note Electrical Conduit PortPage Cradle Switches with Open Designation Using Option SwitchesSlide Switches with on Designation Analog Input Models Switch FunctionsRegulator Assembly Switch SW1 & SW2 Functions & Settings RAISE/LOWER Input ModelsContinuous Signal Incremental SignalSwitch SW1 1-5, Pulse Increments Input FilterStatic or Dynamic Guard Input Guard InputOutput Rate of Change Guard LogicSwitch SW2 2-5, Output Rate Of Change Analog Failure Modes Fail Hold & Fail ZeroFAIL-ZERO Mode Page Field Wiring Terminal Identification For Analog Input Models Terminal Identification For Raise/Lower ModelsAnalog Voltage Input with Guard Analog Current Input 4-20 mA with Guard RAISE/LOWER Inputs with GuardRaise/Lower & Guard Inputs from Relay Contacts DC Power Current Output to FSK Bi-State TransmitterOperating Notes Initial ChecksField Wiring CI-9110 Service Troubleshooting Hints Procedure Setting Output LimitsTest Setup General PrinciplesCalibration Test Setup Calibration PrecautionAnalog Test Setup Preliminary Calibration CheckCurrent Output Span & Load Detailed Calibration for Analog ModelFeedback Zero & Span Pressure Output CheckRaise/Lower Test Setup Detailed Calibration for RAISE/LOWER ModelPCB Reference Drawings CPU Board & Termination Board Reference TableAssembly, Analog Type CPU Board with Current Output Assembly, Raise/Lower Type CPU Board with Current Output Analog Input Model RAISE/LOWER Input ModelAccuracy RAISE/LOWER Models Analog OutputAccuracy Analog Models Stepper Drive MechanismEnvironmental Pressure Regulator AssemblyInstrument Enclosure Range Factory Calibrated withHumidity 10 to 95% over -20to +130 F -29to +55 Range Model 9110 Main Parts Parts Referenced in FigureRemote Set Regulator Actuator Unit Remote Set Regulator Actuator Unit Mounting Parts Remote Set Regulator Assembly Basic Parts Remote SET Regulator Basic PartsGuidelines for System Grounding Basic Ground Rod Installation Noise and Signal Errors General RecommendationsGrounding of Equipment Housing Transients and Interference Grounding of Transmitter Types of Earth Grounds AC Power Grounding System Sandy Soil Dry SoilRocky Soil Several DPCs Mounted in Metal Cabinet with Power Supply Following installation procedures applyGrounding for DPCs and Power Supplies Single Metal Cabinet Multiple DPC Cabinets Powered by Single Power Supply Elements of a Facility Ground System Multiple Clusters of DPC Cabinets Powered by Local Supplies ReferencesPage Remote Set Regulator Model 9110-00A