3.3.1 Continuous Signal
A continuous input signal is one that, when placed in a TRUE state, will cause the output to change until the input is set FALSE. To achieve this mode of operation, all five switches of SW1 should be set to the OPEN position (bottom condition of Table
Figure 3-1 - Option Switches on CPU Board
3.3.2 Incremental Signal
The five switches can be set for any increment from 0.110% per pulse to 1.830% per pulse. The pulses that raise or lower the output perform in real time and are not stored. As a requirement, each pulse must remain in a TRUE state for a period of time necessary for the Remote Set Regulator to reach the new output value. Should the input change from a raise to a lower operation (or
A unit that is set up with a slower rate of change value or a greater percent of full scale change per input pulse will require a longer input pulse. Therefore, the minimum time period required for an ON and OFF pulse to produce an output change is dependent upon the settings of switches SW1
Board Setup |